Specifications

The STB NIB 2212 NIM Module
31004624 8/2009 29
Advantys STB Island Status LEDs
About the Island Status LEDs
The following table describes:
z the island bus condition(s) communicated by the LEDs
z the colors and blink patterns used to indicate each condition
As you refer to the table, keep in mind the following:
z It is assumed that the PWR LED is on continuously, indicating that the NIM is
receiving adequate power. If the PWR LED is off, logic power (see page 37) to
the NIM is off or insufficient.
z Individual blinks are approximately 200 ms. There is a 1-second interval between
blink sequences. Please note:
z blinking: blinks steadily, alternating between 200 ms on and 200 ms off.
z blink 1: blinks once (200 ms), then 1 second off.
z blink 2: blinks twice (200 ms on, 200 ms off, 200 ms on), then 1 second off.
z blink N: blinks N (some number of) times, then 1 second off.
z If the TEST LED is on, either the Advantys configuration software or an HMI
panel is the master of the island bus. If the TEST LED is off, the fieldbus
master has control of the island bus.
Island Status LED Indicators
RUN (green) ERR (red) TEST (yellow) Meaning
blink: 2 blink: 2 blink: 2 The island is powering up (self test in progress).
off off off The island is initializing. The island is not started.
blink: 1 off off The island has been put in the pre-operational state by the
RST button. The island is not started.
blink: 3 The NIM is reading from the removable memory card
(see page 50).
on The NIM is overwriting its Flash memory with the card’s
configuration data. (See note 1.)
off blink: 8 off The contents of the removable memory card are invalid.
blinking (steady) off off The NIM is configuring (see page 43) or auto-configuring
(see page 46) the island bus. The island bus is not started.
blinking off on Auto-configuration data is being written to Flash memory.
(See note 1.)
blink: 3 blink: 2 off Configuration mismatch detected after power up. At least
one mandatory module does not match. The island bus is
not started.