Specifications
Advanced Configuration Features
94
31004624 8/2009
Reserved Sizes (PLC to HMI)
The network transmits data to the HMI as output by writing it to the output data table 
in the process image. This table is shared with data for all output modules on the 
island bus. When the reserved size (PLC to HMI) value is selected, the range of 
available data sizes (in words) appears in the window (see the above figure). The 
maximum size includes both the data sent to the island modules and the PLC to HMI 
data. Therefore, space that you reserve for PLC to HMI data—plus the output data 
for the island bus modules—must not exceed the maximum value. For example, if 
your output modules consume four words of output data, you can reserve only the 
remaining 11 words (out of 15 maximum) of the output data table for the PLC to HMI 
data.
Reserving Data Sizes
To transfer data to the PLC from a Modbus HMI you must reserve sizes for that data. 
To reserve these data sizes:
Step Action Result
1 In the module editor window, select the 
Parameters tab.
2 In the Parameter name column, expand 
the Additional Info Store List by clicking 
on the plus (+) sign.
The configurable NIM parameters 
become visible.
3 Double-click in the Value column next to 
the Reserved Size (Words) of HMI to PLC 
table.
The value is highlighted.
4 Enter a value that represents the data 
size that will be reserved for data sent 
from the HMI panel to the PLC.
The value you enter plus the data size of 
your island can not exceed the maximum 
value. If you accept the default (0), no 
space will be reserved in the HMI table in 
the process image.
5 Repeat the above steps to select a Value 
for the Reserved Size (Words) of PLC to 
HMI table row.
6Press OK when you have entered the 
desired data sizes.