Datasheet

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
27/3/2012
1
Product data sheet
Characteristics
LADR2
time delay auxiliary contact block TeSys D - 1
NO + 1 NC - screw clamp terminals
Main
Range of product TeSys D
TeSys F
Product or component
type
Time delay auxiliary contact block
Product compatibility LC1F
TeSys D contactor
TeSys D control relays
TeSys D reversing contactor
Pole contact
composition
1 NO + 1 NC
Connections - terminals Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: flexible - with cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: flexible - without cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: solid - with cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: solid - without cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: flexible - with cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: flexible - without cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: solid - with cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: solid - without cable end
Complementary
Mounting location Front
[Ui] rated insulation voltage 600 V - certifications UL
690 V - conforming to IEC 60947-5-1
600 V - certifications CSA
[Ue] rated operational voltage 690 V AC 25...400 Hz
[Ith] conventional free air thermal current 10 A at <= 60 °C
Irms rated making capacity 140 A at <= 690 V AC conforming to IEC 60947-5-1
250 A at <= 690 V DC conforming to IEC 60947-5-1
Permissible short-time rating 100 A at -5...60 °C 1 s
120 A at -5...60 °C 500 ms
140 A at -5...60 °C 100 ms
Protection type GG fuse <= 10 A rating according to operational current for Ue <= 690 V
Mechanical durability 5000000 cycles
Minimum switching current 5 mA
Minimum switching voltage 17 V
Non-overlap time 1.5 ms on de-energisation (no overlap between NC and NO contact)
1.5 ms on energisation (no overlap between NC and NO contact)
Timer type Off delay
Time delay range 0.1...30 s
Insulation resistance > 10 MOhm
Product weight 0.060 kg