Data Sheet

[Icw] rated short-time-
withstand current
120 A <= 40 °C 1 min power circuit
240 A <= 40 °C 10 s power circuit
380 A <= 40 °C 1 s power circuit
50 A <= 40 °C 10 min power circuit
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
Associated fuse rating 40 A gG at <= 690 V coordination type 2 for power-
circuit
63 A gG at <= 690 V coordination type 1 for power-
circuit
10 A gG for signalling circuit conforming-
to IEC 60947-5-1
Average impedance 2 mOhm at 50 Hz - Ith 40 A for power circuit
[Ui] rated insulation volt-
age
600 V for power circuit certifications CSA
600 V for power circuit certifications UL
690 V for power circuit conforming to IEC 60947-4-1
690 V for signalling circuit conforming-
to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL
Electrical durability 1.65 Mcycles 25 A AC-3 at Ue <= 440 V
1.4 Mcycles 40 A AC-1 at Ue <= 440 V
Power dissipation per-
pole
3.2 W AC-1
1.25 W AC-3
Protective cover With
Mounting support Plate
Rail
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product certifications BV
CCC
CSA
DNV
GL
GOST
LROS (Lloyds register of shipping)
RINA
UL
2