Datasheet
Product datasheet
Characteristics
LC1D38P7
TeSys D contactor - 3P(3 NO) -
AC
-3 - <= 440 V 38
A
-
230 V AC 50/60 Hz coil
Main
Range
TeSys
Product name
TeSys D
Product or component type
Contactor
Device short name
LC1D
Contactor application
Motor control
Resistive load
Utilisation category
AC
-1
AC
-3
AC
-4
Poles description
3P
Pole contact composition
3 NO
[Ue] rated operational voltage
<= 690 V AC 25...400 Hz for power circuit
<= 300 V DC for power circuit
[Ie] rated operational current
38 A (<= 60 °C) at <= 440 V AC AC-3 for power
circuit
50 A (<= 60 °C) at <= 440 V AC AC-1 for power
circuit
Motor power kW
18.5 kW at 500 V AC 50/60 Hz AC-3
18.5 kW at 660...690 V AC 50/60 Hz AC-3
7.5 kW at 400 V AC 50/60 Hz AC-4
18.5 kW at 380...400 V AC 50/60 Hz AC-3
18.5 kW at 415...440 V AC 50/60 Hz AC-3
9 kW at 220...230 V AC 50/60 Hz AC-3
Motor power hp
10 hp at 230/240 V AC 50/60 Hz for 3 phases
motors
10 hp at 200/208 V AC 50/60 Hz for 3 phases
motors
5 hp at 240 V AC 50/60 Hz for 1 phase motors
20 hp at 480 V AC 50/60 Hz for 3 phases motors
25 hp at 600 V AC 50/60 Hz for 3 phases motors
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
230 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand
voltage
Conforming to IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal
current
50 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
Irms rated making capacity
550 A at 440 V for power circuit conforming to IEC
60947
140 A AC for signalling circuit conforming to IEC
60947-5-1
250 A DC for signalling circuit conforming to IEC
60947-5-1
Rated breaking capacity
550 A at 440 V for power circuit conforming to IEC
60947
[Icw] rated short-time withstand
current
150 A <= 40 °C 1 min power circuit
310 A <= 40 °C 10 s power circuit
430 A <= 40 °C 1 s power circuit
60 A <= 40 °C 10 min power circuit
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
Associated fuse rating
63 A gG at <= 690 V coordination type 1 for power
circuit
63 A gG at <= 690 V coordination type 2 for power
circuit
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
1 / 3