Datasheet

Product datasheet
Characteristics
LC1D80P7
TeSys D contactor - 3P(3 NO) -
AC
-3 - <= 440 V 80
A
-
230 V AC 50/60 Hz coil
Main
Range
TeSys
Product name
TeSys D
Product or component type
Contactor
Device short name
LC1D
Contactor application
Motor control
Resistive load
Utilisation category
AC
-1
AC
-3
AC
-4
Poles description
3P
Pole contact composition
3 NO
[Ue] rated operational voltage
<= 690 V AC for power circuit
<= 300 V DC 25...400 Hz for power circuit
[Ie] rated operational current
125 A (<= 60 °C) at <= 440 V AC AC-1 for power
circuit
80 A (<= 60 °C) at <= 440 V AC AC-3 for power
circuit
Motor power kW
22 kW at 220...230 V AC 50/60 Hz AC-3
37 kW at 380...400 V AC 50/60 Hz AC-3
45 kW at 660...690 V AC 50/60 Hz AC-3
45 kW at 415...440 V AC 50/60 Hz AC-3
55 kW at 500 V AC 50/60 Hz AC-3
45 kW at 1000 V AC 50/60 Hz AC-3
15 kW at 400 V AC 50/60 Hz AC-4
Motor power hp
20 hp at 200/208 V AC 50/60 Hz for 3 phases
motors
7.5 hp at 115 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase
motors
25 hp at 230/240 V AC 50/60 Hz for 3 phases
motors
60 hp at 460/480 V AC 50/60 Hz for 3 phases
motors
60 hp at 575/600 V AC 50/60 Hz for 3 phases
motors
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
230 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand
voltage
Conforming to IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal
current
125 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
Irms rated making capacity
1100 A at 440 V for power circuit conforming to IEC
60947
140 A AC for signalling circuit conforming to IEC
60947-5-1
250 A DC for signalling circuit conforming to IEC
60947-5-1
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC
60947
[Icw] rated short-time withstand
current
135 A <= 40 °C 10 min power circuit
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
640 A <= 40 °C 10 s power circuit
990 A <= 40 °C 1 s power circuit
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
1 / 4

Summary of content (4 pages)