Datasheet

Product datasheet
Characteristics
LC1DLKP7
TeSys LC1D.K capacitor duty contactor - 3P - 20
kVAR
- 415 V -
230 V AC coil
Main
Range
TeSys
Product name
TeSys LC1D.K
Product or component type
Capacitor duty contactor
Device short name
LC1DLK
Contactor application
Power factor correction
Utilisation category
AC
-6B
Poles description
3P
Pole contact composition
3 NO
Device location in system
Line interruption
Inside delta interruption
[Ue] rated operational voltage
<= 690 V AC 50/60 Hz for power circuit
Reactive power rating
21 kvar at 440 V AC 50/60 Hz <= 60 °C
11 kvar at 230 V AC 50/60 Hz <= 60 °C
33 kvar at 660...690 V AC 50/60 Hz <= 60 °C
20 kvar at 400...415 V AC 50/60 Hz <= 60 °C
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
230 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 2 NC for signalling circuit
3 NO early make for power circuit
Electrical durability
300000 cycles at Ue 400 V
200000 cycles at Ue 690 V
Mounting support
DIN rail
Plate
Standards
IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
Product certifications
CCC
CSA
IEC
UL
EAC
KC
Connections - terminals
Control circuit : screw clamp terminals 2 cable(s)
1...2.5 mm² - cable stiffness: flexible - with cable
end
Power circuit : screw clamp terminals 1 cable(s)
1.5...10 mm² - cable stiffness: flexible - without
cable end
Control circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: solid - without cable
end
Control circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: solid - without cable
end
Power circuit : screw clamp terminals 1 cable(s)
1...10 mm² - cable stiffness: flexible - with cable
end
Power circuit : screw clamp terminals 2 cable(s)
1.5...6 mm² - cable stiffness: flexible - without
cable end
Power circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: flexible - with cable end
Power circuit : screw clamp terminals 1 cable(s)
2.5...16 mm² - cable stiffness: solid - without cable
end
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
1 / 2

Summary of content (2 pages)