Datasheet
Product datasheet
Characteristics
LC2D40ABBE
TeSys D reversing contactor - 3P - <= 440 V - 40 A
AC
-3 -
24 V DC coil
Main
Range
TeSys
Product name
TeSys D Green
Product or component type
Reversing contactor
Device short name
LC2D
Contactor application
Motor control
Resistive load
Utilisation category
AC
-1
AC
-3
Device presentation
Preassembled with reversing power busbar
Poles description
3P
Pole contact composition
3 NO
[Ue] rated operational voltage
690 V AC 25...400 Hz for power circuit
[Ie] rated operational current
60 A (<= 60 °C) at <= 440 V AC-1 for power circuit
40 A (<= 60 °C) at <= 440 V AC-3 for power circuit
Motor power kW
11 kW at 220...230 V AC 50 Hz
22 kW at 500 V AC 50 Hz
18.5 kW at 380...400 V AC 50 Hz
22 kW at 415 V AC 50 Hz
22 kW at 440 V AC 50 Hz
30 kW at 660...690 V AC 50 Hz
Motor power hp
5 hp at 230/240 V AC 60 Hz for 1 phase motors
5 hp at 230/240 V AC 60 Hz for 1 phase motors
10 hp at 230/240 V AC 60 Hz for 3 phases motors
3 hp at 115 V AC 60 Hz for 1 phase motors
10 hp at 200/208 V AC 60 Hz for 3 phases motors
30 hp at 460/480 V AC 60 Hz for 3 phases motors
30 hp at 575/600 V AC 60 Hz for 3 phases motors
Control circuit type
DC DC low consumption
[Uc] control circuit voltage
24 V DC
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand
voltage
6 kV conforming to IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal
current
60 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
Irms rated making capacity
800 A at 440 V for power circuit conforming to IEC
60947
140 A AC for signalling circuit conforming to IEC
60947-5-1
250 A DC for signalling circuit conforming to IEC
60947-5-1
Rated breaking capacity
800 A at 440 V for power circuit conforming to IEC
60947
[Icw] rated short-time withstand
current
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
320 A <= 40 °C 10 s power circuit
720 A <= 40 °C 1 s power circuit
72 A <= 40 °C 10 min power circuit
165 A <= 40 °C 1 min power circuit
Associated fuse rating
80 A gG at <= 690 V coordination type 1 for power
circuit
80 A gG at <= 690 V coordination type 2 for power
circuit
10 A gG for signalling circuit conforming to IEC
60947-5-1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
1 / 3