Specifications

42 35010372 10/2010
Environmental Specifications
Specification Value
Ambient operating
temperature (cabinet
interior & panel face)
0 ° C to +40 ° C (32 ° F to 104 ° F) (1)
0 ° C to +50 ° C (32 ° F to 122 ° F) for XBT GT
Storage temperature -20 ° C to + 60 ° C (-4 ° F to 140 ° F)
Damp Heat Withstand +25° C to +60° C / 93% Rh
Air purity (dust)
0.1 mg/m
3
(non-conductive levels)
Pollution degree 2
Corrosive gases Free of corrosive gases
Atmospheric endurance
(XBT GT operation
altitude)
800 hPa to 1,114 hPa (2,000 m [6561 ft] or lower)
Vibration immunity IEC 60068- 2 - 6
z Industry: (XBT GT, XBT GH and XBT GK series)
5Hz to 9Hz 3.5mm, 9Hz to 150Hz 1g.
z Marine: (XBT GT series)
3 Hz to 13 Hz 1mm, 13 Hz to 100 Hz 0,7g.
Electromagnetic
Interference (EMI)
immunity (via EMI
simulator)
1000 Vp-p (except XBT GT7000 series), 1500 Vp-p
for XBT GT7000 series.
Pulse duration: 1 μs
Rise time:1 ns
Concussion Resistance
(XBT GH only)
IEC/EN61131-2 compliant
(147 m/s2 X, Y, Z directions for 3 times)
Drop Resistance
(XBT GH only
IEC 61131-2 compliant
1.0 meter drop - 2 times
Protection (front panel) IP 65 - (IEC 60529) for XBT GT Series, XBT GH
Series, and XBT GK Series
Enclosure type, 4X indoor use with screw
installation fasteners only for XBT GT series and
with spring clips fasteners only for XBT GK series.
Protection (rear panel) IP 20 - (IEC 60529) for XBT GT Series and XBT GK
Series
IP 65 - (IEC 60529) for XBT GH Series
Radiated radio
frequency
electromagnetic field
IEC 61000 - 4 - 3
10 V / m
Electrical fast transient
burst
IEC 61000- 4 - 4
2 kV (power supply and I/O) 1 kV other ports