Application Does Not Go To RUN State
Possible causes:
No POU declared in the task.
ControllerLockout activated.
Resolution:
As POUs are managed by tasks, add a POU to a task:
1. Double click a task in the device view.
2. Click Add POU in the task window.
3. Select the POU you want to execute in the Input Assistant window and click OK.
4. Unlock ControllerLockout in Vijeo Designer.
2 Check that the XBT GT/GK HMI Controller has been detected by your PC:
1. Click Start → Control Panel → System, then select the Hardware tab and click Device Manager,
2. Check that the XBT GT/GK HMI Controller node appears in the list, as shown below:
3. If the XBT GT/GK HMI Controller node does not appear, or if there is an icon in front of the
node, disconnect and reconnect the cable on the controller side.
3 Check that the active path is correct:
1. Double click the controller node in the device view.
2. Check that the XBT GT/GK HMI Controller node appears in bold, not in italic.
If not:
a. Stop the CoDeSys Gateway: right click the icon in the task bar and select Stop Gateway.
b. Disconnect and reconnect the cable on the controller side.
c. Start the CoDeSys Gateway: right click the icon in the task bar and select Start Gateway.
d. Select the gateway in the controller window of SoMachine and click Scan network. Select the
XBT GT/GK HMI Controller node and click Set active path.
NOTE: If your PC is connected to an Ethernet network, its address might have changed. In this case,
the currently set active path is no longer correct and the XBT GT/GK HMI Controller node appears in
italics. Select the XBT GT/GK HMI Controller node and click Resolve Name. When the node no longer
appears in italics. To correct this, click Set Active Path.
Check Action