Schneider Electric Legal Disclaimer The information presented in this manual is not warranted by Schneider Electric to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, Schneider Electric assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this Publication.
Table of Contents Introduction ........................................................................1 Unpack the Cabinet ...........................................................2 Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Please Recycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Important Safety Information . . . . . . . .
Equipment Installation ..................................................... 15 Adjust the Vertical Mounting Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Position the Vertical Mounting Flanges . . . . . . . . . . . . . . . . . . .15 Vertical Mounting Flange Adjustment . . . . . . . . . . . . . . . . . . . .16 Install the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 To install rack-mount equipment in the cabinet: . . . . . . . . . . . .
Introduction The Schneider Electric NetShelter SX 600 mm (23.6 in.) and 750 mm (29.5 in.) wide cabinets are high-quality cabinets for storage of industry-standard (EIA/ECA-310), 19 in. (483 mm) rack-mount hardware, which includes servers and voice, data, networking, internetworking, and power protection equipment. Optional vertical mounting flanges are available for the 750 mm (29.5 in.) wide cabinet for accommodating 23 in. EIA/ECA telecommunications equipment.
Unpack the Cabinet Disclaimer Schneider Electric is not responsible for damage sustained during reshipment of this product. Inspection Inspect the packaging and contents for shipping damage. Make sure that all parts are accounted for. Report any damage immediately to the shipping agent. Report missing contents, damage, or other problems immediately to Schneider Electric or your reseller. Please Recycle The shipping materials are recyclable. Save them for later use, or dispose of them appropriately.
Safety Instructions This manual contains important instructions that must be followed during the installation and customization of the cabinet. WARNING TIP HAZARD • This cabinet is easily tipped. Use extreme caution when unpacking or moving. • Use at least two people to unpack and move the cabinet. • Before moving the cabinet on its casters, load 158 kg (350 lb) of equipment into the bottom of the cabinet for extra stability.
Component Identification ns0609b Cabinet Adjustable vertical 0U accessory channel* Removable and reversible front door Removable rear split doors Nameplate (if equipped) Removable side panel with lock Key for doors and side panels Cabinet frame Vertical mounting flanges Adjustable leveling feet 1070 mm (42.13 in.) roof Hardware bag (see page 5) 1200 mm (47.24 in.) roof Casters * 1200 mm (47.24 in.) deep cabinets include four vertical 0U Accessory Channels.
Hardware Bag Plastic cup washer (60) M6 x 16 Phillips slot screw (60) M5 x 12 screw (4) TORX® T30/#2 Phillips tool NetShelter SX Cabinet - Installation and Customization Manual Cage nut (60) 7 mm (0.28 in.
Side Panels, Roof, and Doors na2591a Side Panels Roof ns1724b X2 6 NetShelter SX Cabinet - Installation and Customization Manual
ns2283a Door Removal ns1604b 1. Unlock the cabinet front door handle and open the door. 2. Disconnect the ground wire and any other wire connections that may interfere with the removal of the doors. 3. The hinges come apart by lifting upward and outward. Slowly lift and pull the door from the cabinet until the hinge pins on the door are free of the hinges on the cabinet frame. Door Installation 1. The doors self-align on hinge pins when properly installed.
Cabinet Installation Move the Cabinet WARNING TIP HAZARD • This cabinet is easily tipped. Use extreme caution when unpacking or moving. • Use at least two people to unpack and move the cabinet. • Before moving the cabinet on its casters, load 158 kg (350 lb) of equipment into the bottom of the cabinet for extra stability. • When moving on its casters, make sure the leveling feet are up and push the cabinet from the front or rear.
Level the Equipment Note: The leveling feet at the corners of the equipment provide a stable base if the floor is uneven, but they cannot compensate for a badly sloped surface. 1. Ensure the cabinet is in its intended location. Remove the front and rear doors. See “Door Removal” on page 7 for instruction. Note: Before removing the front door, unplug the ground wires and any other wire connections that may interfere with the removal of the doors. Notes: 1.
Join the Cabinets Join cabinets with the provided brackets to provide alignment and some added stability. Cabinets may be joined with or without the side panels installed. WARNING TIP HAZARD Joining cabinets provides limited stability to the cabinets. Make sure you secure the cabinet to the floor before installing equipment. Failure to follow these instructions can result in death, serious injury, or equipment damage. 1. Remove the front and rear doors. See “Door Removal” on page 7 for instructions. 2.
Reverse the Front Door Note: The front door can be reversed so that the door opens in the other direction. This procedure assumes that initially, when facing the cabinet, the hinges are on the left and the door is opening from right. ns1758b 1. Remove the handle by removing the screw-plate. Pull the handle from the door. ns1752b 2. Disconnect the ground wire, and any other wire connections. Remove the door from the frame. See “Door Removal” on page 7 for more information. 3.
6. Locate the lock handle. Remove the cam screw, cam washer, and cam. Rotate the cam washer 90 degrees, and the latch 180 degrees. ns1779b ns1766b Install the handle on the door. 7. Remove the nameplate (if equipped) from the door. Install the nameplate at the location shown in the illustrations below. 307 mm (12 in.) ns1612b ns2010a 300 m m 375 m (11.8 in.) (6 m (14 .8 in.
Secure the Cabinet WARNING TIP HAZARD Make sure you secure the cabinet to the floor before installing equipment. Failure to follow these instructions can result in death, serious injury, or equipment damage. To secure the cabinet to the floor, use fastener locations on the outside or inside of the cabinet, and choose from the accessories shown below.
Ground the Cabinet Each cabinet should be bonded directly to a common ground using one of the designated grounding locations (two M6 threaded inserts) at the top or bottom of the cabinet. • Use a Common Bonding Network Jumper kit (for example, Listed [KDER] Panduit® RGCBNJ660PY or equivalent). • Use paint-piercing washers between the ground terminal and the cabinet frame, or remove the paint on the frame under the ground terminals, per NEC NFPA 70 Article 250.12. • Torque the screws to 6.9 N•m (60 lb-in).
Equipment Installation Note: NetShelter SX cabinets are intended for use with Listed equipment. If you install un-Listed equipment, you should evaluate the safety of your configuration. Adjust the Vertical Mounting Flanges Vertical mounting flanges come factory-installed at 737 mm (29 in.), the proper location for use with rack-mountable equipment. The mounting flanges are adjustable towards the front or the rear of the cabinet to accommodate different rails or equipment with other depths.
Vertical Mounting Flange Adjustment WARNING FALLING EQUIPMENT Remove all equipment installed on the vertical mounting flanges before performing any adjustments. Failure to follow these instructions can result in serious injury or equipment damage. 1. Use the provided TORX T30 tool to loosen the top, middle, and bottom TORX screws holding the vertical mounting flange in place. The brackets, all held in place by the TORX screws, will now be loose.
2. Move the mounting flange to the desired location. Vertical mounting flanges adjust in 6 mm (1/4 in.) increments. 3. To align the vertical mounting flange, note the symbol (for example, a diamond) visible through one of the three holes. Only one symbol will be visible. In the factory standard position, a circle symbol is visible. Make sure the same symbol is visible through the corresponding hole at both the top and the bottom of the flange. 4.
Install the Equipment WARNING TIP HAZARD • This cabinet is easily tipped. Make sure you have secured the cabinet to the floor before installing equipment. • Install the heaviest equipment first and toward the bottom of the cabinet to prevent the cabinet from becoming top-heavy. • Do not extend equipment on sliding rails until you have installed 158 kg (350 lb) of equipment into the bottom of the cabinet for stability or until you have installed the stabilizer plate or bolt-down brackets.
Remove the Cable Cutout Covers For NetShelter SX 750 mm (29.5 in.) wide cabinets that include equipment requiring side airflow, on the side of the cabinet nearest the air intake for the equipment (right side in the example below), remove the cable cutout covers from the front vertical mounting flange. Reinstall the covers in the cable cutout holes on the rear vertical mounting flange on the same side of the cabinet.
Cable Management The NetShelter SX cabinet has multiple cable access openings, including on the roof, sides, and bottom. Route, secure, and organize cables using these openings. In addition, two rear vertical 0U cable organizers, or accessory channels, are included with the cabinet. Further cable management accessories are available. Please see www.apc.com, or contact a Schneider Electric re-seller for more information.
Specifications 42U Cabinets AR3100 AR3150 Height 1991 mm (78.39 in.) 1991 mm (78.39 in.) Width 600 mm (23.62 in.) 750 mm (29.53 in.) Depth 1070 mm (42.13 in.) 1070 mm (42.13 in.) Net weight 125.09 kg (275.20 lb) 155.96 kg (343.10 lb) Total open area front door 593 018 mm2 (919.18 in2) 788 972 mm2 (1,222.91 in2) Total open area rear door 669 276 mm2 (1,037.38 in2) 866 920 mm2 (1,343.73 in2) Open area per U front door 14 129 mm2 (21.90 in2) 18 787 mm2 (29.
42U Cabinets, continued AR3300 AR3350 Height 1991 mm (78.39 in.) 1991 mm (78.39 in.) Width 600 mm (23.62 in.) 750 mm (29.53 in.) Depth 1200 mm (47.24 in.) 1200 mm (47.24 in.) Net weight 134.09 kg (295.00 lb) 161.36 kg (355.00 lb) Total open area front door 593 018 mm2 (919.18 in2) 788 972 mm2 (1,222.91 in2) Total open area rear door 669 276 mm2 (1,037.38 in2) 866 920 mm2 (1,343.73 in2) Open area per U front door 14 129 mm2 (21.90 in2) 18 787 mm2 (29.
45U Cabinets AR3105 AR3155 Height 2124 mm (83.62 in.) 2124 mm (83.62 in.) Width 600 mm (23.62 in.) 750 mm (29.53 in.) Depth 1070 mm (42.13 in.) 1070 mm (42.13 in.) Net weight 137 kg (301.40 lb) 155 kg (341 lb) Total open area front door 635 373 mm2 (984.83 in2) 847 212 mm2 (1313.18 in2) Total open area rear door 715 693 mm2 (1109.33 in2) 929 528 mm2 (1440.77 in2) Open area per U front door 14 119 mm2 (21.89 in2) 18 827 mm2 (29.18 in2) Open area per U rear door 15 904 mm2 (24.
45U Cabinets, continued AR3305 AR3355 Height 2124 mm (83.62 in.) 2124 mm (83.62 in.) Width 600 mm (23.62 in.) 750 mm (29.53 in.) Depth 1200 mm (47.24 in.) 1200 mm (47.24 in.) Net weight 141 kg (310.2 lb) 169 kg (371.8 lb) Total open area front door 635 373 mm2 (984.83 in2) 847 212 mm2 (1313.18 in2) Total open area rear door 715 693 mm2 (1109.33 in2) 929 528 mm2 (1440.77 in2) Open area per U front door 14 119 mm2 (21.89 in2) 18 827 mm2 (29.
48U Cabinets AR3157 AR3107 Height 2258 mm (88.90 in.) 2258 mm (88.90 in.) Width 600 mm (23.62 in.) 750 mm (29.53 in.) Depth 1070 mm (42.13 in.) 1070 mm (42.13 in.) Net weight 138.23 kg (304.10 lb) 169.09 kg (372 lb) Total open area front door 676 805 mm² (1,049.05 in²) 900 417 mm2 (1,395.65 in2) Total open area rear door 763 637 mm² (1,183.64 in²) 989 243 mm2 (1,533.33 in2) Open area per U front door 14 103 mm² (21.86 in²) 18 761 mm2 (29.
48U Cabinets, continued AR3307 AR3357 Height 2258 mm (88.90 in.) 2258 mm (88.90 in.) Width 600 mm (23.62 in.) 750 mm(29.53 in.) Depth 1200 mm (47.24 in.) 1200 mm (47.24 in.) Net weight 149.55 kg (329.00 lb) 185.45 kg (408 lb) Total open area front door 676 805 mm² (1,049.05 in²) 900 417 mm2 (1,395.65 in2) Total open area rear door 763 637 mm² (1,183.64 in²) 989 243 mm2 (1,533.33 in2) Open area per U front door 14 103 mm² (21.86 in²) 18 761 mm2 (29.
Limited Factory Warranty The limited warranty provided by Schneider Electric in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business. Terms of Warranty Schneider Electric warrants its products to be free from defects in materials and workmanship for a period of five years (two years in Japan) from the date of purchase.
Worldwide Customer Support Customer support for this or any other product is available at no charge in any of the following ways: • Visit the Schneider Electric Web site to access documents in the Schneider Electric Knowledge Base and to submit customer support requests. – www.schneiderelectric.com (Corporate Headquarters) Connect to localized Schneider Electric Web sites for specific countries, each of which provides customer support information. – www.schneiderelectric.