Conditions
The most important test and limit values for mechanical conditions are listed in the
following table:
EMC Conditions The most important tests and limit values for EMC conditions are listed in the
following tables:
EN 61131-2 Mechanical Tests
Vibration test, operating: 5 Hz to 9 Hz / 3.5 mm, 9 Hz to
150 Hz / 1g
6.3.5.1 Immunity vibration test: 10 Hz to 150 Hz, 1 g, EUT
operating, 10 cycles per axis
6.3.5.2 Immunity shock test: 15g, 11ms, EUT operating, 2 cycles
per axis
EN 61131-2 Noise Immunity Test
6.3.6.2.1 IEC/EN 61000-4-2 ESD test: 4 kV contact/ 8 kV air discharge
6.3.6.2.2 IEC/EN 61000-4-3 RFI test (10 V/m): 26 MHz to 1 GHz, 80% AM
6.3.6.2.3 IEC/EN 61000-4-4 Burst test: 2 kV power supply / 1 kV signal lines
6.3.6.2.4 IEC/EN 61000-4-12 Damped oscillatory wave immunity test: 1 kV
IEC/EN 61000-6-2 Noise Immunity Test
IEC/EN 61000-4-6 Radio frequency common mode: 10 V
150 kHz to 80 MHz, AM
IEC/EN 61000-4-3 900 MHz pulses
IEC/EN 61000-4-5 Surge: 1 kV, 0.5 kV
IEC/EN 61000-6-4 Noise Emission Test
EN50011 Class A Emission test: radiated, conducted