User's Manual

PD100 Partial Discharge Tag Operation
Result: The PD100 is in Zigbee factory reset state.
Communication Lost
The PD100 has lost communication with the Panel Server or gateway for more
than 15 minutes when:
The operation LED is green (blinking or xed).
The network status LED ashes red.
The PD100 periodically monitors its communication state with the coordinator in
accordance with product specications. At any time, if communication is lost with
the coordinator, the Zigbee LED starts fast-blinking in red.
NOTE: If the PD100 detects a communication loss with the coordinator, it may
take up to ve minutes before the PD100 updates its status if communication
with the coordinator is restored.
Unpairing the PD100
To manually unpair the PD100:
1. Press the operation button for more than 8 s.
2. When the network status LED turns xed orange, release the button.
To pair the PD100 to a Panel Server or gateway, see how to connect an existing
Zigbee network, page 23.
Diagnostic Mode
In diagnostic mode, the PD100 does not monitor the cubicle.
DANGER
HAZARD OF ELECTRIC SHOCK
The diagnostic must be made by skilled personnel from Schneider Electric,
using additional devices and sensors. To make a diagnostic, contact Schneider
Electric.
Failure to follow these instructions will result in death or serious injury.