PowerLogic™ PM5100 Series Power and Energy Meter User Guide EAV15105 - EN03 04/2014 PQS
Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
PowerLogic™ PM5100 series user guide Table of Contents Chapter 1: Introduction Power and Energy Meter Hardware ................................................................................. 9 Parts and Accessories .................................................................................................. 9 Box Contents ................................................................................................................ 9 Firmware .....................................................
Table of Contents PowerLogic™ PM5100 series user guide Chapter 7: Alarms About Alarms .................................................................................................................. 51 1-Second Alarms ......................................................................................................... 51 Unary Alarms ............................................................................................................... 53 Alarm Priorities ..................................
PowerLogic™ PM5100 series user guide Table of Contents Meter firmware version ................................................................................................... 88 MID-protected setup parameters .................................................................................... 88 Lock-protected setup parameters ................................................................................... 88 Lock-protected functions ..................................................................
Table of Contents 8 PowerLogic™ PM5100 series user guide © 2014 Schneider Electric All Rights Reserved
PowerLogic™ PM5100 user guide Chapter 1—Introduction Chapter 1—Introduction This user guide explains how to operate and configure a PowerLogic™ PM5100 Series Power and Energy Meter.
Chapter 1—Introduction 10 PowerLogic™ PM5100 user guide © 2014 Schneider Electric All Rights Reserved
PowerLogic™ PM5100 series user guide Chapter 2—Safety Precautions Chapter 2—Safety Precautions Before You Begin Installation, wiring, testing and service must be performed in accordance with all local and national electrical codes. This section contains important safety precautions that must be followed before attempting to install, service, or maintain electrical equipment. Carefully read and follow the safety precautions outlined below.
PowerLogic™ PM5100 series user guide Chapter 2—Safety Precautions • • Increase the separation between the equipment and receiver. • Consult the dealer or an experienced radio/TV technician for help. Connect the equipment to an outlet on a circuit different from that to which the receiver is connected. This Class B digital apparatus complies with Canadian ICES-003.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Chapter 3—Hardware Reference This section supplements the meter’s installation sheet and provides additional information about the meter’s physical characteristics and capabilities. Models, Features and Options Table 3 –1: PM5100 Series - Models, Features and Options PM5100 series Features and Options PM5100 PM5110 PM5111 Cl 0.5S Cl 0.5S Cl 0.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Energy Values* Accumulated Active, Reactive and Apparent Energy Received/Delivered; Net and absolute Demand Values* Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Current average Active power Reactive power Apparent power Demand calculation (Sliding, fixed and rolling block, thermal
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Power Factor Class 0.5 as per IEC 61557-12 1 Voltage Harmonics Class 5 as per IEC 61557-12 1 Voltage THD/thd Class 5 as per IEC 61557-12 1 Current Harmonics Class 5 as per IEC 61557-12 1 Current THD/thd Class 5 as per IEC 61557-12 1 MID Directive (2004/22/EC) Annex B and Annex D (PM5111) Class C Input-voltage (up to 1.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Pollution degree Altitude For indoor use only 2 2000 m CAT III / 3000 m CAT II Electromagnetic Compatibility 3 Electrostatic discharge Immunity to radiated fields Immunity to fast transients Immunity to surge Conducted immunity 150kHz to 80MHz Immunity to magnetic fields Immunity to voltage dips Radiated emissions Conducted emissions IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6 IEC 61000-4-8 IEC 61000-4-11 FCC pa
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards. • Turn off all power supplying this device before working on it. • Always use a properly rated voltage sensing device to confirm that all power is off. • Do not exceed the device’s ratings for maximum limits.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Mounting the PM5100 The meter is designed to be mounted inside a 1/4-DIN panel cutout. 1. Inspect the gasket (installed around the perimeter of the front display) and make sure it is secured properly and not damaged. 2. Insert the meter through the mounting hole. +0.8 -0 +0.8 - 0.0 92.0 mm 92.0 m.0 m 3. Line up the tabs of the retainer clips with the slots on either side of the meter.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Meter wiring For wiring instructions and safety precautions, see the meter installation sheet that was shipped with your meter, or download a copy at www.schneider-electric.com. • Wire connections to the meter’s voltage inputs, control power, digital output, and RS485 communications are terminated using the supplied pluggable wire connectors.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Recommended cables Communication Make RS-485 20 Belden Part code Description 3105A Multi-Conductor - EIA Industrial RS-485 PLTC/CM 3106A Multi-Conductor - EIA Industrial RS-485 PLTC/CM © 2014 Schneider Electric All Rights Reserved
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Wiring Diagrams 1PH 1PH2WLN 1PH2WLL ( I1 ) ( I2 ) ( I3 ) V1 V2 V3 VN - + - + ( I1 ) ( I2 ) V1 V2 V3 VN - + + B - + - + A A A + -+ + - - + B B B + + L1 L1 L L2 L2 N N + L1 L2 L N - + - + + + + ( I1 ) - ( I2 ) - ( I3 )- V1 V2 V3 VN B B A A + L N - - + - + ( I1 () I1 () I2()I2 () I3( )I3 ) V1V3 V2VN V3 VN V1 V2 ( I3 ) - + ( I1 ) ( I2 ) ( I3 ) V1 V2 V3 VN A - + 1PH3WLL with N + + 3PH3W
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Symbol Description 500 mA fused disconnect / circuit breaker (not supplied) Shorting block (not supplied) PT primary fuses and disconnect switch (not supplied) * Indicates wiring for a balanced system NOTE: • Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the operator. • The fuses / circuit breakers must be rated for the installation voltage and sized for the available fault current.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Power system setup parameters Power system description — Meter setting Direct connect maximum Symbol # of VTs (if required) UL IEC 347 V L-N 400 V L-N 1 VT 600 V L-L 600 V L-L 1VT 347 V L-N / 600 V L-L 400 V L-N / 690 V L-L 2VT 600 V L-L 600 V L-L 2 VT 600 V L-L 600 V L-L 2 VT 600 V L-L 600 V L-L 2 VT 600 V L-L 600 V L-L 2 VT 600 V L-L 600 V L-L 2 VT 240 V L-N / 415 V L-N / 480 V L-L 240 V L-N / 415 V L-N / 480
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Power system setup parameters (continued) Power system description — Meter setting Direct connect maximum Symbol 3-phase 4-wire Delta center-tapped — 3PH4W Dlt Ctr Tp # of VTs (if required) UL IEC 240 V L-N / 415 V L-N / 480 V L-L 240 V L-N / 415 V L-N / 480 V L-L 3 VT 347 V L-N / 600 V L-L 347 V L-N / 600 V L-L 3 VT or 2 VT 347 V L-N / 600 V L-L 400 V L-N / 690 V L-L 3 VT or 2 VT 347 V L-N / 600 V L-L 347 V L-N / 600 V L-L
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Balanced system considerations In situations where you are monitoring a balanced 3-phase load, you may choose to connect only one or two CTs on the phase(s) you want to measure, and then configure the meter so it calculates the current on the unconnected current input(s). NOTE: For a balanced 4-wire Wye system, the meter’s calculations assume that there is no current flowing through the neutral conductor.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference RS-485 wiring Connect the devices on the RS-485 bus in a point-to-point configuration, with the (+) and (-) terminals from one device connected to the corresponding (+) and (-) terminals on the next device. RS-485 wiring C + 120 Ω Master Slaves C + D0 (-) D1 (+) 120 Ω RS-485 cable Use a shielded 1.5 twisted pair or 2 twisted pair RS-485 cable to wire the devices.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference Related topics • To configure RS-485 communications, see “Setting up serial communications” on page 34. Digital outputs The meter is equipped with a digital output port (D1).
PowerLogic™ PM5100 series user guide 28 Chapter 3—Hardware Reference © 2014 Schneider Electric All Rights Reserved
PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup Chapter 4—Front panel display and meter setup The front panel display lets you use the meter to perform various tasks such as setting up the meter, displaying data screens, acknowledging alarms, or performing resets.
Chapter 4—Front panel display and meter setup PowerLogic™ PM5100 series user guide Related topics • See “Setting up the alarm / energy pulsing LED” on page 39 for details on using the front panel to switch the LED mode for alarming or energy pulsing applications. • See “Alarm / energy pulsing LED setup” on page 48 for details on using ION Setup to switch the LED mode for alarming or energy pulsing applications.
PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup Menu tree This summarizes the meter screens (IEEE menus shown, with the corresponding IEC menus in parentheses — see “Setting up regional settings” on page 35).
Chapter 4—Front panel display and meter setup PowerLogic™ PM5100 series user guide Meter setup screen navigation The meter’s front panel buttons and display screen allow you to navigate and configure the meter’s setup parameters. The following illustration shows one of the meter setup screens. Basic setup screen In this example, the down arrow ( ) indicates there are more parameters below the selected option ( ). Press the down arrow button to display additional parameters.
PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup Basic setup menu tree Maint Reset Meter Setup Comm Basic 1. Navigate to Maint > Setup. 2. Enter the setup password (default is “0000”), then press OK. 3. Navigate to Meter > Basic. 4. Move the cursor to point to the parameter you want to modify, then press Edit. 5. Modify the parameter as required, then press OK. 6.
Chapter 4—Front panel display and meter setup PowerLogic™ PM5100 series user guide Related topics • See “Configuring the basic setup parameters” on page 32 for meter basic setup instructions. Communications setup After wiring the meter’s serial communications port, you can configure these ports so you can connect to the meter remotely and use device configuration software such as ION Setup to configure the meter.
PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup HMI settings The HMI (human-machine interface) setup screens allow you to: • • • control the general appearance and behavior of the display screens, change the regional settings, or change the meter passwords. Setting up the display You can change the display screen’s contrast or the screen backlight and timeout settings.
Chapter 4—Front panel display and meter setup PowerLogic™ PM5100 series user guide Regional settings menu tree Maint Reset Meter Setup Comm Alarm I/O Displ HMI Region Clock Pass 1. Navigate to Maint > Setup. 2. Enter the setup password (default is “0000”), then press OK. 3. Navigate to HMI > Region. 4. Move the cursor to point to the parameter you want to modify, then click Edit. 5. Modify the parameter as required, then press OK. 6.
PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup Password setup menu tree Maint Reset Meter Setup Comm Alarm I/O Displ HMII Region Clock Pass 1. Navigate to Maint > Setup. 2. Enter the setup password (default is “0000”), then press OK. 3. Navigate to HMI > Pass. 4. Move the cursor to point to the parameter you want to modify, then press Edit. 5. Modify the parameter as required, then press OK. 6.
Chapter 4—Front panel display and meter setup PowerLogic™ PM5100 series user guide 3. Navigate to Clock. 4. Move the cursor to point to the parameter you want to modify, then press Edit. 5. Modify the parameter as required, then press OK. 6. Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK. Clock setup parameters Parameter Format Description Set the current date using the format displayed on screen, where MM = month, DD = day and YY = year.
PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup Advanced setup parameters Parameter Values Label Load Timer Setpt (A) Pk I dmd for TDD (A) Description ----- This label identifies the device, e.g., “Power Meter”. You cannot use the front panel to edit this parameter. Use ION Setup to change the device label. 0 - 99999 Specifies the minimum average current at the load before the timer starts.
Chapter 4—Front panel display and meter setup PowerLogic™ PM5100 series user guide Related topics • See “Setting up the alarm / energy pulsing LED” on page 39 for details on setting up the LED for alarms. Output setup The meter’s input/output (I/O) ports extend the capabilities of the meter. The I/O ports can be configured using the front panel or ION Setup. Related topics • See “Input / Output” on page 47 for a comprehensive description and setup instructions using the front panel.
PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup Power or current demand setup parameters (continued) Parameter Select Dig Output Clock Sync Time Values None, Digital Output D1 0 - 2359 Description Select which digital output the end of demand interval pulse should be sent to. Applies only to clock sync methods (these synchronize the demand interval to the meter’s internal clock). Define what time of day you want to synchronize the demand 8.
Chapter 4—Front panel display and meter setup 42 PowerLogic™ PM5100 series user guide © 2014 Schneider Electric All Rights Reserved
PowerLogic™ PM5100 series user guide Chapter 5—Viewing Meter Data Chapter 5—Viewing Meter Data You can view meter data from the meter’s front panel display, a web browser, or through software. Viewing meter data from the front panel The Summary screen displays real-time values for average voltage and current (Vavg, Iavg), total power (Ptot) and energy consumption (E Del).
Chapter 5—Viewing Meter Data PowerLogic™ PM5100 series user guide Related topics • See “Current demand” on page 65. Volts [U-V] V L-L [U] Line-to-line voltage for each phase. V L-N [V] Line-to-neutral voltage for each phase.
PowerLogic™ PM5100 series user guide Chapter 5—Viewing Meter Data THD THD Amps [I], V L-L [U], V L-N [V] THD (ratio of harmonic content to the fundamental) for current, line-to-line voltage, and line-to-neutral voltage. Amps [I], V L-L [U], V L-N [V] thd (ratio of harmonic content to the rms value of total harmonic content) for current, line-to-line voltage, and line-to-neutral voltage. thd Related topics • See “Power quality” on page 67.
Chapter 5—Viewing Meter Data PowerLogic™ PM5100 series user guide Maint Setup Meter, Comm, Alarm, I/O, HMI, Clock Diag Info, Meter, Cl Pwr, PhAng Setup screens for meter configuration. Diagnostic screens provide meter information, status and event data for troubleshooting. The PhAng screen displays a graphical representation of the power system the meter is monitoring. Related topics • • • See “Meter resets” on page 77. See “Front panel display and meter setup” on page 29.
Chapter 6—Input / Output PowerLogic™ PM5100 series user guide Chapter 6—Input / Output This section describes the meter’s output features. The meter is equipped with one digital output port. After you wire the meter’s output ports, you can configure the port so you can use the meter to perform I/O functions.
Chapter 6—Input / Output PowerLogic™ PM5100 series user guide Configuring digital outputs using the front panel You can use the front panel to configure the digital outputs. Digital output setup menu tree Maint Reset Meter Setup Comm Alarm LED I/O D Out HMI Clock 1. Navigate to Maint > Setup. 2. Enter the setup password (default is “0000”), then press OK. 3. Navigate to I/O > D Out. 4. Press Edit. 5. Press + and - to scroll through the modes None or Energy.
PowerLogic™ PM5100 series user guide Chapter 6—Input / Output 3. Navigate to I/O configuration > Energy Pulsing. 4. Select the LED or a digital output to configure and click Edit. The setup screen is displayed. 5. Enter a descriptive name for the digital output’s Label. 6. Configure the other setup parameters as required. 7. Click Send to save your changes.
Chapter 6—Input / Output PowerLogic™ PM5100 series user guide Alarm / energy pulsing LED parameters available through the front panel Parameter Values Description Active Del Active Rec Active Del + Rec Reactive Del Reactive Rec Parameter Select which accumulated energy channel to monitor and use for energy pulsing. Reactive Del + Rec Apparent Del Apparent Rec Apparent Del + Rec 5. Press 6. Press 50 or to modify the parameter as required, then press OK. to exit. Press Yes to save your changes.
PowerLogic™ PM5100 series user guide Chapter 7—Alarms Chapter 7—Alarms This section describes the alarm features on PM5100 series Power and Energy meters. About Alarms The ! icon appears in the upper-right corner of the meter display when an alarm is active. If the energy/alarm LED has been configured for alarms, the energy/alarm LED flashes when an alarm is active. See “Alarm / energy pulsing LED setup” on page 48 for more information.
PowerLogic™ PM5100 series user guide Chapter 7—Alarms • • Dropout Setpoint (magnitude) Dropout Time Delay (in seconds) Table 7–1: List of Standard 1-Second Over/Under Alarms Alarm Number 52 Alarm Label 01 Over Current, Phase 02 Under Current, Phase 03 Over Current, Neutral 04 Over Current, Ground 05 Over Voltage, L-L 06 Under Voltage, L-L 07 Over Voltage, L-N 08 Under Voltage L-N 09 Over kW 10 Over kVAR 11 Over kVA 12 Lead PF, True 13 Lag PF, True 14 Lead PF, Disp 15 Lag
PowerLogic™ PM5100 series user guide Chapter 7—Alarms Many of the 1-second alarms are three-phase alarms. Alarm setpoints are evaluated for each of the three phases individually, but the alarm is reported as a single alarm. The alarm pickup occurs when the first phase exceeds the alarm pickup magnitude for the pickup time delay. The alarm is active as long as any phase remains in an alarm state. The alarm dropout occurs when the last phase drops below the dropout magnitude for the dropout time delay.
PowerLogic™ PM5100 series user guide Chapter 7—Alarms • Low priority—if a low priority alarm occurs, the alarm LED and the alarm icon blink only while the alarm is active. No alarm message is displayed. • No priority—if an alarm is set up with no priority, no visible representation appears on the display. Alarms with no priority are not entered in the alarm Log. If multiple alarms with different priorities are active at the same time, the display shows the alarms in the order they occurred.
PowerLogic™ PM5100 series user guide Chapter 7—Alarms Setting Up 1-Second Alarms To set up a standard alarm: 1. Press 1-Sec. The 1-second alarm Select screen appears. 2. Press ▼ and ▲ to scroll through the list of standard 1– second alarms. 3. Press Edit to select an alarm to be configured. 4. Press Edit to select Pickup Setpoint. 5. Press + to increment the active digit through the numerals 0-9. 6. Press to enter the selected value for the active digit and move to the next digit to the left. 7.
PowerLogic™ PM5100 series user guide Chapter 7—Alarms Setting Up 1-Second Alarms (continued) 17. Press ▼ to select Priority, then press Edit. 18. Press + and - to scroll through priority options None, High, Medium, or Low. NOTE: See “Alarm Priorities” on page 53 for more information. 19. Press OK to set the priority. ▲ 20. Press to save all alarm selections and return to the previous screen. ▲ to save all 1-second 21. Press alarm selections.
PowerLogic™ PM5100 series user guide Setting Up Unary Alarms Chapter 7—Alarms To set up unary alarms: 1. Press Unary. The unary alarm Select screen appears. 2. Press ▼ and ▲ to scroll through the list of unary alarms. 3. Press Edit to select an alarm to be configured. 4. Press Edit to select Enable. 5. Press + and - to scroll between Yes and No. 6. Press OK to enable or disable the alarm. 7. Press ▼ to select Priority. 8. Press + and - to scroll through priority options Low, None, High, or Medium.
PowerLogic™ PM5100 series user guide Chapter 7—Alarms Viewing Active Alarms and Alarm Counters To view active alarms or alarm counters: 1. Scroll through the menu list at the bottom of the screen until you see Alarm. 2. Press Alarm. 3. Press the button beneath Active or Count. 4. Press ▼ and ▲ to scroll through the alarm list. ▲ 5. Press to return to the previous screen.
PowerLogic™ PM5100 series user guide Chapter 7—Alarms Viewing Unacknowledged Alarms and the Alarm History Log To view the unacknowledged alarms or the alarm history log: 1. Scroll through the menu list at the bottom of the screen until you see Alarm. 2. Press Alarm. 3. Press the button beneath Unack or Hist. 4. Press ▼ and ▲ to scroll through the list of primary alarm events. 5. Press Detail to view pickup and dropout event details. 6. Press ▼ and ▲ to scroll through the pickup and dropout event details.
PowerLogic™ PM5100 series user guide 60 Chapter 7—Alarms © 2014 Schneider Electric All Rights Reserved
PowerLogic™ PM5100 series user guide Chapter 8—Measurements and calculations Chapter 8—Measurements and calculations This section describes how the meter processes measured and calculated data. Real-time readings The power and energy meter measures currents and voltages, and reports in real time the RMS (Root Mean Squared) values for all three phases and neutral. The voltage and current inputs are continuously monitored at a sampling rate of 64 points per cycle.
Chapter 8—Measurements and calculations PowerLogic™ PM5100 series user guide Power factor min/max convention The meter uses the following convention for power factor minimums and maximums: • For negative PF readings, the minimum PF value is the measurement closest to -0 for PF readings between -0 to -1. For positive PF readings, the minimum PF value is the measurement closest to +1 for PF readings between +1 to +0.
PowerLogic™ PM5100 series user guide Chapter 8—Measurements and calculations IEEE mode In IEEE mode, the PF sign is determined by the type of load (inductive or capacitive) contributing to the reactive power component of apparent power. PF sign is positive (+) for capacitive loads (leading power factor). PF sign is negative (-) for inductive loads (lagging power factor). Related topics • • To change the HMI mode, see “Setting up regional settings” on page 35.
Chapter 8—Measurements and calculations PowerLogic™ PM5100 series user guide The following illustration shows the different ways power demand is calculated using the block interval method. In this example, the interval is set to 15 minutes. Block interval demand example Demand value is the average for the last completed interval Calculation updates every 15 seconds 15-minute interval 15 30 45 60 . Time (sec) ..
PowerLogic™ PM5100 series user guide Chapter 8—Measurements and calculations 8:00 am, select 0800 (in hhmm format). When setting up this type of demand, you can choose Clock Sync Block (clock-synchronized block demand) or Clock Sync Roll Blk (clock-synchronized rolling block demand). Clock Sync Roll Blk requires that you specify a subinterval. Thermal demand Thermal demand calculates the demand based on a thermal response, which imitates the function of thermal demand meters.
Chapter 8—Measurements and calculations PowerLogic™ PM5100 series user guide Predicted demand example Beginning of interval Demand for last completed interval 15-minute interval Predicted demand if load is added during interval; predicted demand increases to reflect increased demand Partial Interval Demand Predicted demand if no load is added.
PowerLogic™ PM5100 series user guide Chapter 9—Power quality Chapter 9—Power quality This section describes the meter’s power quality features and how to access power quality data. The meter measures voltage and current harmonics up to the 15th harmonic, and calculates Total Harmonic Distortion (THD) and Total Demand Distortion (TDD and tdd). Harmonics overview Harmonics are integer multiples of the fundamental frequency of the power system.
Chapter 9—Power quality PowerLogic™ PM5100 series user guide THD and thd calculations The meter supports two methods of calculating total harmonic distortion: THD and thd. THD is a quick measure of the total distortion present in a waveform and is the ratio of harmonic content to the fundamental. The meter uses the following equation to calculate THD: HC THD = -------- 100 H1 Where H1 is equal to the fundamental harmonic. thd is an alternate method for calculating total harmonic distortion.
PowerLogic™ PM5100 series user guide Chapter 9—Power quality Example: 7th to 15th harmonics for line-to-neutral voltage Phase A Phase B Phase C The vertical axis of the harmonics graph indicates the harmonic’s magnitude as a percentage of the fundamental harmonic, and is scaled based on the largest harmonic displayed. At the top of each vertical bar is a marker that shows the maximum value of the harmonic.
Chapter 9—Power quality PowerLogic™ PM5100 series user guide Related topics 70 • See “Front panel display and meter setup” on page 29 for front panel menu navigation details. • Search PM5100 Modbus register list at www.schneider-electric.com to download the Modbus map.
PowerLogic™ PM5100 series user guide Chapter 10—Verifying accuracy Chapter 10—Verifying accuracy All meters are tested and verified at the factory in accordance with International Electrotechnical Commission (IEC) and American National Standards Institute (ANSI) standards. Your digital power meter does not require re-calibration. However, in some installations a final accuracy verification of the meters is required, especially if the meters will be used for revenue or billing applications.
Chapter 10—Verifying accuracy PowerLogic™ PM5100 series user guide temperature before calibration to help ensure that the meters will reach their optimal accuracy at operating temperature. Most high precision electronic equipment requires a warm up time before it reaches its specified performance levels. Energy meter standards allow the manufacturers to specify meter accuracy derating due to ambient temperature changes and self-heating.
PowerLogic™ PM5100 series user guide Chapter 10—Verifying accuracy Verifying accuracy test The following are guidelines for testing the meter; your meter shop may have specific testing methods. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards. • Turn off all power supplying this device before working on it.
Chapter 10—Verifying accuracy PowerLogic™ PM5100 series user guide 6. Depending on the method selected for counting the energy pulses, configure the meter’s alarm / energy LED or one of the digital outputs to perform energy pulsing. Set the meter’s energy pulse constant so it is in sync with the reference test equipment. 7. Perform accuracy verification on the test points. Run each test point for at least 30 seconds to allow the test bench equipment to read an adequate number of pulses.
PowerLogic™ PM5100 series user guide Chapter 10—Verifying accuracy Where: • • EM = energy measured by the meter under test ES = energy measured by the reference device or energy standard. NOTE: If accuracy verification reveals inaccuracies in your meter, they may be caused by typical sources of test errors. If there are no sources of test errors present, please contact your local Schneider Electric representative.
Chapter 10—Verifying accuracy PowerLogic™ PM5100 series user guide (Maximum pulse frequency)- = 3600 25- = 0.009 kW Maximum Ptot = 3600 -----------------------------------------------------------------------------------------------------------Kmax 9,999,999 Test points The meter should be tested at full and light loads and at lagging (inductive) power factors to help ensure testing over the entire range of the meter. The test amperage and voltage input rating are labeled on the meter.
PowerLogic™ PM5100 series user guide Chapter 11—Meter resets Chapter 11—Meter resets Reset commands clear the meter’s onboard data logs and related registers. Meter resets are typically performed after you make changes to the meter’s basic setup parameters (such as power system, frequency, or PT/CT settings), to clear invalid or obsolete data in preparation for putting the meter into active service. The meter reset commands are grouped into two categories: Global Resets and Single Resets.
Chapter 11—Meter resets PowerLogic™ PM5100 series user guide Single resets Single resets allow you to clear data only in a specific register or register type. 1. Navigate to Maint > Reset. 2. Move the cursor to point to Single Reset, then press Select. 3. Move the cursor to point to the parameter you want to reset, then press Reset. If there are additional options for the parameter, press Select, move the cursor to point to the option you want, then press Reset.
PowerLogic™ PM5100 series user guide Chapter 11—Meter resets Alarm counter options (continued) Alarm counter Frequency Option Over Frequency Under Frequency Description Select which alarm counter register to reset from the frequency alarm condition counters. Meter Powerup Unary Meter Reset Meter Diagnostic Select which alarm counter register to reset from the unary alarm condition counters.
Chapter 11—Meter resets 80 PowerLogic™ PM5100 series user guide © 2014 Schneider Electric All Rights Reserved
PowerLogic™ PM5100 User Guide Chapter 12—Maintenance and Upgrades Chapter 12—Maintenance and Upgrades Chapter 12 — Maintenance and Troubleshooting Password Recovery Alarms If you lose your password, contact technical support for password recovery assistance: • • Global-PMC-Tech-support@schneider-electric.com (00) + 1 (250) 544-3010 NOTE: Be sure to include your power meter’s serial number in your e-mail or have it readily available when calling technical support.
PowerLogic™ PM5100 series user guide Chapter 12—Maintenance and Upgrades Additional Meter Status Information Meter 1. Scroll to Maint in the menu list. 2. Press Maint. 3. Press Diag. 4. Press Meter. 5. View the power meter status. ▲ 6. Press to return to the Maintenance screen. Control Power 1. Scroll to Maint in the menu list. 2. Press Maint. 3. Press Diag. 4. Press Cl Pwr. 5. View control Power information. ▲ 6. Press to return to the Maintenance screen.
PowerLogic™ PM5100 User Guide Chapter 12—Maintenance and Upgrades Troubleshooting The information in Table 12–1 on page 84 describes potential problems and their possible causes. It also describes checks you can perform or possible solutions for each. After referring to this table, if you cannot resolve the problem, contact your local Schneider Electric sales representative for assistance.
PowerLogic™ PM5100 series user guide Chapter 12—Maintenance and Upgrades Table 12–1: Troubleshooting Potential Problem Possible Cause Possible Solution Go to [Maint] > [Diag]. Event messages When the maintenance (wrench) icon The maintenance (wrench) display to indicate the reason the icon is is illuminated, it indicates an event icon is illuminated on the illuminated. Note these event messages and has occurred which may require power meter display. call the Technical Support or contact your attention.
Chapter 13—MID Compliance This section applies only to PM5111(referred to in the section as the meter) and contains descriptions and procedures that supplement the meter installation sheet. The information contained here supports the meter’s declaration of compliance with the Measuring Instruments Directive (2004/22/EC).
Chapter 13—MID Compliance PowerLogic™ PM5100 series Intended use Indoor use only, permanently mounted in residential, commercial or light industrial applications, where levels of vibration and shock are of low significance Mechanical environment M1 Electromagnetic (EMC) environment E2 Active Accuracy Class (kWh) C(kWh) System types (for MID-compliant applications) • • Voltage at voltage terminals 3-phase 4-wire Wye grounded 3-phase 3-wire Wye ungrounded 3-phase 4-wire Wye grounded 3 x 63.
PowerLogic™ PM5100 series Chapter 13—MID Compliance Related topics • See “Meter mounting” on page 17 and “Meter wiring” on page 19 for additional information. Installing the terminal covers The voltage and current terminal covers help prevent tampering with the meter’s voltage and current measurement inputs. The terminal covers enclose the terminals, the conductor fixing screws and a suitable length of the external conductors and their insulation.
Chapter 13—MID Compliance PowerLogic™ PM5100 series Related topics • See “Front panel display and meter setup” on page 29 for detailed information on front panel menu navigation, LED indicators and display screen notification icons. Meter firmware version You can access information about the meter’s OS and RS firmware versions by navigating to Maint > Diag > Info.
PowerLogic™ PM5100 series Chapter 13—MID Compliance Lock-protected functions Menu Resets Sub-menu Lock-protected function Global Resets • • Meter Initialization (all) Energies Single Resets • Energy Setting up the PM5111 You must configure all the lock-protected setup parameters before locking the meter. When the meter is locked, those setup parameters cannot be edited. Basic setup menu See “Configuring the basic setup parameters” on page 32 to perform basic setup.
Chapter 13—MID Compliance PowerLogic™ PM5100 series 3. Enter your lock password. NOTE: The default password is 0000. To set up a new password see “Setting up lock password” on page 90. 4. Press + and - to scroll between Active and Inactive. 5. Press OK to select the option. 6. Select Yes to confirm the selected option, and exit the screen. On activating the lock, a lock icon appears on the upper left corner of the screen. 7. Make sure you record and store the lock password in a secure location.
PowerLogic™ PM5100 series user guide Glossary Glossary Terms accumulated energy—energy accumulates as either delivered to the customer or received from the customer. active alarm—an alarm that has been set up to trigger the execution of a task or notification when certain conditions are met. An icon in the upper-right corner of the power meter indicates that an alarm is active (!).
PowerLogic™ PM5100 series user guide Glossary partial interval demand—equal to energy accumulated thus far in the interval divided by the length of the complete interval. peak demand current—highest demand current measured in amperes since the last reset of demand. peak demand real power—highest demand real power measured since the last reset of demand. peak demand—highest demand measured since the last reset of demand.
PowerLogic™ PM5100 series user guide Glossary Abbreviations A—Ampere Amps—Amperes Comms—Communications CPT—Control Power Transformer CT—Current Transformer D Out—Digital Output DMD—Demand DO—Drop Out F—Frequency GMT—Greenwich Mean Time Hz—Hertz I—Current I/O—Input/Output Imax—Current maximum demand k_h— kWh, kVARh or kVAh depending on the energy parameter selected kVA—Kilovolt-Ampere kVAD—Kilovolt-Ampere demand kVAR—Kilovolt-Ampere reactive kVARD—Kilovolt-Ampere reactive demand kVARH—Kilovolt-Ampere react
PowerLogic™ PM5100 series user guide Glossary Pwr—Power Q—Reactive power Qd—Reactive power demand RS—Firmware reset system version S—Apparent power SN—Power meter serial number Sd—Apparent power demand Sec—Secondary Sub-I—Subinterval TDD—Total Demand Distortion THD—Total Harmonic Distortion U—Voltage line to line V—Volts VT—Voltage Transformer (also known as PT–Potential Transformer) VAR—Volt ampere reactive Vmax—Maximum voltage Vmin—Minimum voltage 94 © 2014 Schneider Electric All Rights Reserved
PowerLogic and Schneider Electric are trademarks or registered trademarks of Schneider Electric in France, the USA and other countries. • This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations. • If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired. Schneider Electric 35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex www.schneider-electric.