Specifications

63230-507-201A1 Power Meter 750
03/2007 Appendix B—Register List
© 2007 Schneider Electric All Rights Reserved
37
4011
Voltage, L-N, 3P
Average
1 Integer RO N V Volt/Scale 0-32767
4012 Current, 3P Average 1 Integer RO N I Amp/Scale 0-32767
4013 Frequency 1 Integer RO N 0.01 Hz 4500-6500 Derived from Phase A
4020 Current, A 1 Integer RO N I Amp/Scale 0-32767
4021 Current, B 1 Integer RO N I Amp/Scale 0-32767
4022 Current, C 1 Integer RO N I Amp/Scale 0-32767
4023 Current, N 1 Integer RO N I Amp/Scale 0-32767
4030 Voltage, A-B 1 Integer RO N V Volt/Scale 0-32767
4031 Voltage, B-C 1 Integer RO N V Volt/Scale 0-32767
4032 Voltage, C-A 1 Integer RO N V Volt/Scale 0-32767
4033 Voltage, A-N 1 Integer RO N V Volt/Scale 0-32767
4034 Voltage, B-N 1 Integer RO N V Volt/Scale 0-32767
4035 Voltage, C-N 1 Integer RO N V Volt/Scale 0-32767
4036 Real Power, A 1 Integer RO N W kW/Scale 0-32767 Signed Net Consumption
4037 Real Power, B 1 Integer RO N W kW/Scale 0-32767 Signed Net Consumption
4038 Real Power, C 1 Integer RO N W kW/Scale 0-32767 Signed Net Consumption
4039 Apparent Power, A 1 Integer RO N W kVA/Scale 0-32767
4040 Apparent Power, B 1 Integer RO N W kVA/Scale 0-32767
4041 Apparent Power, C 1 Integer RO N W kVA/Scale 0-32767
4042 Reactive Power, A 1 Integer RO N W kVAR/Scale 0-32767 Signed Net Consumption
4043 Reactive Power, B 1 Integer RO N W kVAR/Scale 0-32767 Signed Net Consumption
4044 Reactive Power, C 1 Integer RO N W kVAR/Scale 0-32767 Signed Net Consumption
4045 Current, A, THD 1 Integer RO N 0.1 % 0-10000
4046 Current, B, THD 1 Integer RO N 0.1 % 0-10000
Table B– 2: Register Listing—Metered Data (continued)
Metered Data
Reg Name Size Type Access NV Scale Units Range Notes
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.