Data Sheet

Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Minimum pulse duration 100 ms (with load in parallel)
30 ms
Insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1
Reset time 120 ms (on de-energisation)
Immunity to microbreaks <= 10 ms
Power consumption in VA 3 VA at 240 V AC
Power consumption in W 1.5 W at 240 V DC
Switching capacity in VA 2000 VA
Minimum switching current 10 mA 5 V DC
Maximum switching current 8 A
Maximum switching voltage 250 V AC
Electrical durability 100000 cycles for 8 A at 250 V AC-1
100000 cycles for 2 A at 24 V DC-1
Mechanical durability 10000000 cycles
[Uimp] rated impulse withstand voltage 5 kV for 1.2...50 µs conforming to IEC 60664-1
Delay response < 100 ms
Creepage distance 4 kV/3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data MTTFd = 205.4 years
B10d = 190000
Mounting position Any position
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Status LED Green LED backlight (steady) for dial pointer indication
Yellow LED (steady) for output relay energised
Yellow LED (fast flashing) for timing in progress and output relay de-energised
Yellow LED (slow flashing) for timing in progress and output relay energised
Width 22.5 mm
Product weight 0.1 kg
Time delay type A, Ac, Act, At, Aw, C, Ct, D, Di, Dit, Diw, Dt, Dw, H, Ht, Hw, W, Wt
Contacts type and composition 1 C/O
Functionality Multifunction
Environment
Dielectric strength 2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with-
basic insulation conforming to IEC 61812-1
Standards IEC 61812-1
UL 508
Directives 2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
Product certifications CCC
CE
CSA
GL
UL
RCM
EAC
China RoHS
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -40...70 °C
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front face) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Vibration resistance 20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn (not operating) (duration = 11 ms) conforming to IEC 60068-2-27
5 gn (in operation) (duration = 11 ms) conforming to IEC 60068-2-27
2