RE22R1MYMR Product data sheet Characteristics Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Multi-function Timing Relay - 0.
30...300 s Control type Rotary knob Diagnostic button External potentiometer [Us] rated supply voltage 24...240 V AC/DC at 50/60 Hz Input voltage <= 2.4 V Voltage range 0.85...1.1 Us Supply frequency 50...60 Hz (+/- 5 %) Connections - terminals Screw terminals : 1 x 0.5...1 x 3.3 mm², AWG 20...AWG 12 solid cable without cable end Screw terminals : 2 x 0.5...2 x 2.5 mm², AWG 20...AWG 14 solid cable without cable end Screw terminals : 1 x 0.2...1 x 2.5 mm², AWG 24...
Product certifications EAC CCC China RoHS GL CSA CE RCM UL Ambient air temperature for operation -20...60 °C Ambient air temperature for storage -40...70 °C IP degree of protection IP20 (terminals) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front face) conforming to IEC 60529 Pollution degree 3 conforming to IEC 60664-1 Vibration resistance 20 m/s² (f = 10...
Product data sheet Dimensions Drawings Dimensions 4 RE22R1MYMR
Product data sheet Connections and Schema RE22R1MYMR Wiring Diagram 5
Product data sheet Technical Description RE22R1MYMR Function A: Power On-Delay Description On energisation of power supply, the timing period T starts. After timing, the output(s) R close(s).The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Product data sheet Technical Description RE22R1MYMR Function Ac: On-Delay & Off-Delay with Control Signal Description After energisation of power supply and energization of Y1 causes the timing period T to start. At the end of this timing period, the output(s) R close(s). When deenergization of Y1, the timing T starts. At the end of this timing period T,the output(s) R revert(s) to its/their initial position.
Product data sheet Technical Description RE22R1MYMR Function Act: On-Delay & Off-Delay with Control Signal & With Pause / Summation Control Description After energisation of power supply and energization of Y1 causes the timing period T to start and the timing can be interrupted / paused each time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R close(s).
Product data sheet Technical Description RE22R1MYMR Function At: Power On-Delay with Pause / Summation Control Description On energisation of power supply, the timing period T starts.Timing can be interrupted / paused each time X1 energizes.Except for RE17*, RE22R2AMU, RE22R2MMW, RE22R2MMU, RE22R2MJU, timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R close(s).
Product data sheet Technical Description RE22R1MYMR Function Aw : Power On-Delay With Retrigger / Restart Control Description On energisation of power supply, the timing period T starts.At the end of the timing period T, the output(s) R close(s).Energization of Y1 makes the output(s) R open(s).Deenergization of Y1 restarts timing period T.At the end of timing period T, the output(s) R close(s).
Product data sheet Technical Description RE22R1MYMR Function C: Off-Delay Relay with Control Signal Description After energisation of power supply and energization of Y1 causes output(s) R close(s). When Y1 deenergizes, timing T starts.At the end of this timing period T,the output(s) R revert(s) to its/their initial position.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Product data sheet Technical Description RE22R1MYMR Function Ct: Off-Delay Relay with Control Signal & With Pause / Summation Control Description After energisation of power supply and energization of Y1 cause output(s) R close(s).When Y1 deenergizes, timing starts and the timing can be interrupted / paused each time X1 energizes. When the cumulative total of time periods elapsedreaches the pre-set value T, the output(s) R revert(s) to its/their initial state.
Product data sheet Technical Description RE22R1MYMR Function D: Symmetrical Flashing Relay (Starting Pulse Off) Description On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for the same timing duration T.This cycle is repeated indefintely until power supply removal.Specially for RE17*, RE22R2AMU, RE22R2MMW, RE22R2MMU, RE22R2MJU,this D function can only be initiated by energizing Y1 permanently.
Product data sheet Technical Description RE22R1MYMR Function Dt: Symmetrical Flashing Relay (Starting Pulse Off) & With Pause / Summation Control Description On energisation of power supply, output(s) R starts at its/their initial state for timing duration T and the timing can be interrupted / paused each time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, then changes to output(s) R close(s).
Product data sheet Technical Description RE22R1MYMR Function DW: Symmetrical Flashing Relay (Starting Pulse Off) & With Retrigger / Restart Control Description On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for the same timing duration T.This cycle is repeated indefintely until power supply removal.
Product data sheet Technical Description RE22R1MYMR Function Di: Symmetrical Flashing Relay (Starting Pulse On) Description On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T then revert(s) to its/their initial state for the same timing duration T.This cycle is repeated indefintely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Product data sheet Technical Description RE22R1MYMR Function Dit: Symmetrical Flashing Relay (Starting Pulse On) & With Pause / Summation Control Description On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T and the timing can be interrupted / paused each time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, then revert(s) to its/their initial state.
Product data sheet Technical Description RE22R1MYMR Function Diw: Symmetrical Flashing Relay (Starting Pulse On) & With Retrigger / Restart Control Description On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T then revert(s) to its/their initial state for the same timing duration T.This cycle is repeated indefintely until power supply removal.
Product data sheet Technical Description RE22R1MYMR Function H: Interval Relay Description On energisation of power supply, output(s) R close(s) and timing period T starts.At the end of the timing period T, the output(s) R revert(s) to its/ their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Product data sheet Technical Description RE22R1MYMR Function Ht: Interval Relay & With Pause / Summation Control Description On energisation of power supply, output(s) R close(s) and timing period T starts.The timing can be interrupted / paused each time X1 energizes.
Product data sheet Technical Description RE22R1MYMR Function Hw: Interval Relay & with Retrigger / Restart Control Description On energisation of power supply, output(s) R close(s) and timing period T starts.At the end of the timing period T, the output(s) R revert(s) to its/their initial state.At any state of the output(s) R when Y1 energizes followed by deenergizes, the output(s) R close(s) then restarts the same operation as described at the beginning.
Product data sheet Technical Description RE22R1MYMR Function W: Interval Relay with Control Signal Off Description After energisation of power supply and on energization of Y1 following by denergization of Y1, the output(s) R close(s) and starts the timing T.At the end of the timing period, the output(s) R revert(s) to its/their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Product data sheet Technical Description RE22R1MYMR Function Wt: Interval Relay with Control Signal Off & with Pause / Summation Control Description After energisation of power supply and on energization of Y1 following by denergization of Y1, the output(s) R close(s) and starts the timing T.Timing can be interrupted / paused each time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state.