Manual

Table Of Contents
Configuring Battery Characteristics and Battery Charging
975-0560-01-01 Revision B 2–3
Modifying Configurable Settings
Configurable settings are identified by square brackets [ ] around the values
along the right side of the screen.
To select and change a configurable setting:
1. On the menu, press the up arrow or down arrow button to highlight the
setting you want to change.
2. Press Enter to highlight the current value of the setting.
3. Press the up arrow or the down arrow button to change the value. Hold down
the button to scroll through a large range of values quickly.
The previously set value appears with an asterisk (*) beside it.
4. Press Enter to select the value.
Configuring Battery Characteristics and Battery Charging
From various menus in the SCP you can:
Enable battery equalization.
Configure your battery type, voltage, and amp-hour capacity.
Configure a custom battery type by adjusting settings for each battery
charge stage and fine-tuning temperature-compensated charging.
Monitor battery temperature.
WARNING
HAZARD OF FIRE AND EXPLOSION
Battery charging settings must be configured by qualified personnel in
accordance with the battery manufacturer's recommended charging
instructions.
Failure to follow these instructions can result in death or serious injury.
CAUTION
BATTERY DAMAGE
The charge controller is incapable of determining battery type and cannot
warn against or disallow incorrect settings. Carefully check the settings for
bulk, absorption, float, and equalization charge against the battery
specifications. Incorrect settings can damage the battery or shorten battery
life.
Failure to follow these instructions can result in equipment damage.