Configuring the Auxiliary Output
975-0560-01-01 Revision B 2–9
To display the Aux menu auxiliary settings, select Advanced Settings > Aux
Settings.
Table 2-4 Aux menu settings
Setting Values Default Description
Manual Aux ManualOff
ManualOn
Automatic
ManualOff Sets the operating mode for the auxiliary output. When
set to Automatic, the auxiliary output will operate
according to the selected trigger source. You can
toggle the auxiliary relay between NC and NO at any
time by selecting ManualOn or ManualOff.
Note: The remaining settings in this table are only visible when Manual Aux is set to Automatic.
Trig Src Configurable:
LowBattV
HighBattV
LowArrayV
HighArrayV
LowBattTemp
HighBattTemp
HighHsTemp
Not configurable:
Fault
GroundFlt1
GroundFlt2
InputOVFlt
InputOVErr
InputOVWrn
OutputOVErr
OutputOVWrn
OutputOCErr
BattOTErr
BattOTWrn
BattUTWrn
HsOTErr
HsOTWrn
AmbOTErr
AmbOTWrn
CapOTErr
FanErr
FanFlt
OutputUVErr
OutputUVWrn
InputOCErr
OutputOCFlt
NetPSFlt
LowBattV Sets the desired condition to activate the auxiliary
output. Changing Trig Src while the auxiliary output is
already in the triggered state resets the auxiliary output.
If Trig Src is set to LowBattV or HighBattV, then
changing battery voltage (see Table 2-1 on page 2–4)
will reset Trigger Level and Clear Level to their
default values.
For a description of the non-configurable faults, errors,
and warnings that you can set for Trig Src, see Table
3-4, “Fault messages” on page 3–6, Table 3-5, “Error
messages” on page 3–7, and Table 3-6, “Warning
messages” on page 3–9.