Viewing Active Faults, Errors, and Warnings
975-0560-01-01 Revision B 3–5
The following faults do not disable normal operation:
• Fan over voltage
• Fan over current
• Fan under voltage
• Fan under current
• Network power supply
Most warnings, errors, and faults clear automatically once the condition that
caused them goes away. However, the following faults must be cleared manually:
• Auxiliary power supply
• Ground fault protection
• Input over voltage
• Output over current
• Fan over voltage
• Fan over current
• Fan under voltage
• Fan under current
• Network power supply
To view the complete list of active faults, errors, and warnings:
1. On the Select Device menu, scroll to System Settings, and then press
Enter.
The System Settings menu opens.
2. Scroll to View Fault List or View Warning List, and then press Enter.
The fault/error or warning menu opens.
3. Press the down button to view additional fault, error, or warning messages. If
there are no active faults, errors, or warnings, no messages are displayed.
To manually clear a fault, error, or warning:
1. On the Select Device menu, scroll to System Settings, and then press
Enter.
The System Settings menu opens.
2. Scroll to Clear All Flts/Wrns, and then press Enter.
1
1.Additional steps are required for a ground fault. See “GroundFlt1” in Table 3-4.