Operation
3–8 975-0560-01-01 Revision B
InputOVErr
(Input over voltage
error)
F9 Input voltage has exceeded the input over voltage shut off value,
which is dependent upon temperature measured on the heatsink
(Vin High Threshold in Figure 3-2 on page 3–10). The error clears
itself when the input voltage falls below the input over voltage
restart value (Vin Restart Threshold in Figure 3-2 on page 3–10).
OutputUVImmErr
(Output under
voltage immediate
error)
F10 Output voltage has fallen below 15.8 VDC. The error clears itself
when the voltage rises above 19.0 VDC for 1 second.
OutputUVErr
(Output under
voltage error)
F11 24 V System: Output voltage has fallen below 18.0 VDC. The error
clears itself when the voltage rises above 19.0 VDC for 1 second.
48 V System: Output voltage has fallen below 36.0 VDC. The error
clears itself when the voltage rises above 38.0 VDC for 1 second.
AuxPSErr
Auxiliary power
supply error
F26 Auxiliary power supply is not within its expected operating range.
The error clears itself after 1 second and the auxiliary power
supply will attempt to restart.
HsOTErr
(Heat sink over
temperature error)
F55 Heat sink temperature has risen above 90 °C (194 °F) for
5 seconds. The error clears itself when the heat sink temperature
falls below 80 °C (176 °F) for 30 seconds.
SetupErr F69 Multiple charge controllers connected to the Xanbus network have
the same device number. The error will clear when the operator
changes the device numbers of the duplicate charge controllers.
The device number can be changed in the Multi Unit Config
screen of the SCP.
OutputOVErr
(Output over
voltage error)
F70 24 V System: Output voltage has risen above 33.0 VDC for
1 second. The error clears itself when the voltage falls below 32.0
VDC for 1 second.
48 V System: Output voltage has risen above 65.0 VDC for
1 second. The error clears itself when the voltage falls below 64.0
VDC for 1 second.
OutpFastOCErr
(Fast output over
current error)
F71 Output current has risen above 117.5 ADC. The error clears itself
after 5 seconds. If the error is triggered three times in a span of 30
seconds, then it must be cleared manually.
OutpSlowOCErr
(Slow output over
current error)
F73 Output current has risen above 90.0 ADC for 10 milliseconds. The
error clears itself after 5 seconds.
Table 3-5 Error messages
Display Text
(Description) Error ID Definition