Installation Guide
Table Of Contents
- Conextâ„¢ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Operation
3–16 975-0638-01-01 Rev A
Changing Operational Settings
The following table shows the various settings you can change to effectively
operate the Conext SW inverter/charger.
To navigate to the Conext SW Setup menu:
1. From the System Status screen (see 1A), press Enter to view the Select
Device menu. Go to step 2.
Or
From the Conext SW Home screen (see1B), press Enter. The Conext SW Setup
menu appears.
2. Highlight the Conext SW device name, and then press Enter.
Figure 3-7 Navigate To Conext SW Setup Menu
Select Device
System Settings
CSW4024
Device 2
Device 3
Device n
XW SCP
Clock
CSW4024 00:Setup
Meters
Inverter
Search Mode
Charger
Force Chg State
Equalize
Mode
Clear Faults/Warnings
View Device Info
Basic Settings
[Enabled]
[Disabled]
[Enabled]
[Disabled]
[Operating]
System Status
Battery
BatLev
Load
AC1
13.8A 24.0V
E--F
1750W
240V 1750W
menu 12:53PM Aug 13
CSW4024 00: Home
Status
Battery
Load
AC In
Invert
-16.4A 26.2V
1750W
0.0V 0W
setup system
1A 1B
2
ConextSW-NA-OwnersGuide.book Page 16 Thursday, December 20, 2012 2:00 PM