Installation Guide
Table Of Contents
- Conext™ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuring Basic Settings
975-0638-01-01 Rev A 4–7
Configuring Basic Settings
An overview of the Conext SW Basic Settings menu structure is shown below.
Figure 4-3 Menu Map of the Conext SW Basic Settings
[*Flooded] [Gel] [AGM]
[*250Ah] [50Ah] to [2000Ah]
[*80%] [10%] to [100%]
[*3Stage] or [2StgNoFloat]
[*25.0V] [22.0V]to [27.0V]
[*30.0A] [5.0A]to [30.0A]
[*21.0V] [20.0V]to [24.0V]
CSW4024 00: Basic
Batt Type
Batt Capacity
Max Chg Rate
Charge Cycle
ReCharge Volts
AC In Breaker
Low Batt Cut Out
[Flooded]
[220Ah]
[80%]
[3Stage]
[25.0V]
[30.0A]
[21.0V]
Follow procedures on “To select and change a configurable setting:” on
page 4–4 to change the settings.
Table 4-1 Setting Defaults and Ranges
Model SW 2524 120/240 SW 4024 120/240
Item Default Min Max Default Min Max
Batt Type Flooded Flooded, Gel,
AGM, Custom
Flooded Flooded, Gel,
AGM, Custom
Batt Capacity 250Ah 50Ah 2000Ah 440Ah 50Ah 2000Ah
Max Chg Rate 100% 10% 100% 100% 10% 100%
Charge Cycle 3Stage 3Stage,
2StgNoFloat
3Stage 3Stage,
2StgNoFloat
ReCharge Volts 25.0V 22.0V 27.0V 25.0V 22.0V 27.0V
AC In Breaker 30A 5A 30A 30A 5A 30A
Low Batt Cut
Out
21.0V 20.0V 24.0V 21.0V 20.0V 24.0V
ConextSW-NA-OwnersGuide.book Page 7 Thursday, December 20, 2012 2:00 PM