Configuration via SCP
4–8 975-0638-01-01 Rev A
Table 4-2 Basic Settings
Item Description
Batt Type Sets the system battery chemistry and type: Flooded,
AGM, and Gel.
Batt Capacity Selects the system battery capacity in amp hours.
Max Chg Rate Sets the percentage of the maximum DC output current
that is available to the charger. The maximum DC output
current for different models is:
SW 2524 120/240 — 65 ADC
SW 4024 120/240 — 90 ADC
If multiple Conext SWs are charging the same battery
bank, set each inverter's Max Chg Rate to 1/n of the
desired charge rate (where n is the number of inverter/
chargers).
Charge Cycle Sets the charging method: 3-Stage (bulk, absorption,
float) or 2StgNoFloat (bulk, absorption, no float).
ReCharge Volts Sets the recharging volts to tell the charger to initiate
charging when the battery drains past the value setting.
AC In Breaker Sets the breaker limit of incoming AC (generator or grid).
Low Batt Cut Out Low Battery Cut Out (LBCO) controls when the inverter
stops producing AC output due to a low battery voltage
condition. The inverter will stop producing AC output only
after this level has been reached for the period of time set
by the LBCO Delay. This setting is not temperature
compensated.