Installation Guide
Table Of Contents
- Conext™ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuring Advanced Settings
975-0638-01-01 Rev A 4–13
Charger Settings Menu
The Charger Settings menu provides options for configuring the Conext SW to
operate from your battery bank.
Figure 4-5 Charger Settings Menu Screen
Table 4-5 Setting Defaults and Ranges
Model SW 2524 120/240 SW 4024 120/240
Item Default Min Max Default Min Max
Batt Type Flooded Flooded, Gel,
AGM, Custom
Flooded Flooded, Gel,
AGM, Custom
Custom Settings See page 4–18. See page 4–18.
Batt Capacity See page 4–7. See page 4–7.
Max Chg Rate 100% 10% 100% 100% 10% 100%
Charge Cycle 3Stage 3Stage,
2StgNoFloat
3Stage 3Stage,
2StgNoFloat
Default Batt
Temp
Warm Hot, Warm, Cold Warm Hot, Warm, Cold
ReCharge Volts 25.0V 22.0V 27.0 25.0V 22.0V 27.0V
Absorb Time 180min 1min 480min 180min 1min 480min
Auto Chg Enable Enabled Enabled,
Disabled
Enabled Enabled,
Disabled
Chg Block Start 12:00AM n/a 12:00AM n/a
Chg Block Stop 12:00AM n/a 12:00AM n/a
CSW4024 00: Chg
Batt Type
Custom Settings
Batt Capacity
Max Chg Rate
Charge Cycle
Default Batt Temp
ReCharge Volts
Absorb Time
Auto Chg Enable
Chg Block Start
Chg Block Stop
[Flooded]
[220Ah]
[100%]
[3-Stage]
[Warm]
[25.0V]
[180min]
[Enabled]
[hh:mm AM]
[hh:mm AM]
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
Gen Support
Multi Unit Config
Restore Defaults
Adv Features
[*80%] [1%] to [100%]
[*220Ah] [50Ah] to [2000Ah]
[*3-Stage] or [2StgNoFloat]
[*Warm] [Hot] [Cold]
[*25.0V] [22.0V] to [27.0V]
[*180min] [1min] to [480min]
[*Enabled] or [Disabled]
[*Flooded] [Gel] [AGM] [Custom]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.
ConextSW-NA-OwnersGuide.book Page 13 Thursday, December 20, 2012 2:00 PM