Installation Guide
Table Of Contents
- Conext™ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuration via SCP
4–20 975-0638-01-01 Rev A
AC Settings
The AC Settings menu configures the voltage and frequency limits for AC In.
These are the limits at which the Conext SW considers input voltage qualified—
that is, suitable for charging batteries or powering loads. If the input voltage is
not qualified according to these settings, the Conext SW transfers from using AC
input to inverting.
Figure 4-7 AC Settings Menu Screen
Table 4-9 Setting Defaults and Ranges
Model SW 2524 120/240 SW 4024 120/240
Item Default Min Max Default Min Max
ACIn Breaker 30A 5A 30A 30A 5A 30A
ACIn Lo Volt 95V 78V 115V 95V 78V 115V
ACIn Hi Volt 135V 125V 140V 135V 125V 140V
ACIn Lo Freq 55Hz 44Hz 59Hz 55Hz 44Hz 59Hz
ACIn Hi Freq 65Hz 61Hz 70Hz 65Hz 61Hz 70Hz
AC Qualify Time 5sec 5sec 300sec 5sec 5sec 300sec
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
Gen Support
Multi Unit Config
Restore Defaults
Adv Features
CSW4024 00: AC
ACIn Breaker
ACIn Lo Volt
ACIn Hi Volt
ACIn Lo Freq
ACIn Hi Freq
AC Qualify Time
[30.0A]
[190.0V]
[270.0V]
[55Hz]
[65Hz]
[5sec]
[*190.0V] [156.0V] to [230.0V]
[*30A] [5A] to [30A]
[*270.0V] [250.0V] to [280.0V]
[*55Hz] [44Hz] to [59Hz]
[*55Hz] [61Hz] to [70Hz]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.
Table 4-10 AC Settings menu
Item Description
ACIn Breaker Sets the AC Input breaker size, based on the size of the
installed AC breaker at the source. The Breaker size setting
must not exceed the capacity of the AC source such as the
grid or a generator. The Conext SW limits the maximum input
current to this setting by derating its charging current. If the
connected loads exceed the breaker setting, the AC breaker
trips. The breaker may not trip if Gen Support is enabled and
Gen Amps is configured not to exceed the AC source’s rated
output current.