Configuration via SCP
4–28 975-0638-01-01 Rev A
Using the Advanced Features
The default inverter AC output frequency is 60 Hz.
To change the inverter AC output frequency to 50 Hz:
1. Put the system in Standby mode. See “To change an operational setting:” on
page 3–18.
2. Change the EuroFreq to Enabled. See “To select and change a configurable
setting:” on page 4–6.
3. Restore the system to Operating mode. See “To change an operational
setting:” on page 3–18.
Figure 4-11 Adv Features Menu Screen
Table 4-13 Adv Features Description and Values
a
a.Applies to all Conext SW models.
Item Description Default Range
EuroFreq When enabled, sets the
AC output frequency to
a constant 50Hz.
Disabled Enabled,
Disabled
CSW4024 00: Adv Fea
EuroFreq [Disabled]
[*Disabled] [Enabled]
Follow procedures on “To select and change a configurable
setting:” on page 4–6 to change the settings.
NOTICE
EQUIPMENT DAMAGE
Do not change the frequency to 50 Hz unless the equipment and appliances
connected to the inverter’s output can operate in this frequency setting.
Failure to follow these instructions can result in equipment damage.
IMPORTANT: Restoring to default (see “Restoring Factory Default Settings” on
page 4–27) means that the AC output frequency will change back to 60 Hz.