Installation Guide
Table Of Contents
- Conext™ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuration via SCP
4–28 975-0638-01-01 Rev A
Using the Advanced Features
The default inverter AC output frequency is 60 Hz.
To change the inverter AC output frequency to 50 Hz:
1. Put the system in Standby mode. See “To change an operational setting:” on
page 3–18.
2. Change the EuroFreq to Enabled. See “To select and change a configurable
setting:” on page 4–6.
3. Restore the system to Operating mode. See “To change an operational
setting:” on page 3–18.
Figure 4-11 Adv Features Menu Screen
Table 4-13 Adv Features Description and Values
a
a.Applies to all Conext SW models.
Item Description Default Range
EuroFreq When enabled, sets the
AC output frequency to
a constant 50Hz.
Disabled Enabled,
Disabled
CSW4024 00: Adv Fea
EuroFreq [Disabled]
[*Disabled] [Enabled]
Follow procedures on “To select and change a configurable
setting:” on page 4–6 to change the settings.
NOTICE
EQUIPMENT DAMAGE
Do not change the frequency to 50 Hz unless the equipment and appliances
connected to the inverter’s output can operate in this frequency setting.
Failure to follow these instructions can result in equipment damage.
IMPORTANT: Restoring to default (see “Restoring Factory Default Settings” on
page 4–27) means that the AC output frequency will change back to 60 Hz.