Installation Guide
Table Of Contents
- Conextâ„¢ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuration Sheet
975-0638-01-01 Rev A 4–29
Configuration Sheet
SETTING DESCRIPTION DEFAULT
YOUR SETTING
Inverter Settings Low Batt Cut Out
Select battery voltage below which batteries will be cut out
21.0V
LBCO Delay
Select the time delay before low battery cut out is engaged
10sec
Hi Batt Cut Out
Select the voltage above which batteries will be cut out
29.0V
Search Watts
Select Watts at which level Search Mode triggers on
50W
Search Delay
Select delay time before Search Mode triggers on
2sec
Inv Block Start
Sets the time to halt inverting
12:00AM
Inv Block Stop
Sets the time to resume inverting
12:00AM
Charger Settings Batt Type
Select your battery type (FLOODED, GEL, AGM, Custom)
Flooded
Custom Settings
Makes BATTERY CUSTOM SETTINGS screen visible
--
Eqlz Support
Enable battery EQUALIZE function
Enabled
Eqlz Voltage
Select maximum EQUALIZE voltage
32.0V
Bulk Voltage
Select maximum BULK charge voltage
28.8V
Absorb Voltage
Select maximum ABSORPTION charge voltage
28.8V
Float Voltage
Select maximum FLOAT charge voltage
27.0V
Batt Temp Comp
Select BATTERY TEMPERATURE COMP coefficient
-54mV/C
Batt Capacity
Select battery bank capacity
220Ah
Max Chg Rate
Select maximum charge rate
100%
Charge Cycle
Select 2 or 3 stage charge cycle
3Stage
Default Batt Temp
Select system default battery temp setting
Warm
ReCharge Volts
Select voltage at which charger will initiate a charge cycle
25.0V
Absorb Time
Sets the maximum Absorption time
180min
Auto Chg Enable
Select automatic charging, overrides Charger setup
Enabled
Chg Block Start
Sets the time to halt charging
12:00AM
Chg Block Stop
Sets the time to resume charging
12:00AM
AC Settings AC Breaker
Select AC Input current limit
30A
AC Lo Volt
Select lowest acceptable AC voltage
190V
AC Hi Volt
Select highest acceptable AC voltage
270V
AC Lo Freq
Select lowest acceptable AC frequency
55Hz
AC Hi Freq
Select highest acceptable AC frequency
65Hz
AC Qualify Time
Sets charger waiting time
5sec
Generator Support GenSup Mode
Enables Generator Support function
Disabled
GenSup Amps
Generator current level at which Generator Support Starts
24A
Multi Unit Config Dev Name
Select unique device Name for each unit
CSW4024
CSW2524
Dev Number
Select unique device number for each unit
00
Invtr Mode
Select Master or Slave designation for each unit
Master
AC In
Select AC source type
Gen1
Battery
Identify batteries
HouseBatt1
Restore Defaults --
Restores all system default settings
--
Advanced Features EuroFreq
Sets AC output frequency to 50 Hertz
Disabled
ConextSW-NA-OwnersGuide.book Page 29 Thursday, December 20, 2012 2:00 PM