Installation Guide
Table Of Contents
- Conext™ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Troubleshooting the Conext SW via the SCP
975-0638-01-01 Rev A 5–7
Table 5-3 provides a detailed description of the fault detection messages and
solutions. If you are unable to resolve the problem after referring to this table,
contact customer service.
Table 5-3 Fault Detection Messages
Code Message Type Cause Solution
F1
AC Output under
voltage
Escalating Auto
fault detection.
Must occur 3 times
in 30 seconds
before becoming a
manual fault
detection.
Inverter voltage is
under 210 volts.
Remove excessive load.
F2
AC Output over
voltage
Escalating Auto
fault detection.
Must occur 3 times
in 30 seconds
before becoming a
manual fault
detection.
Inverter voltage is
over 255 volts.
Check if there is an external
power source that is running
parallel to the inverter’s
output.
F17
AC Backfeed (L1) Manual AC backfeed from
welded relay on
Line 1.
Service required.
F18
AC Backfeed (L2) Manual AC backfeed from
welded relay on
Line 2.
Service required.
F44
Battery Over
Temperature
Automatic Battery
temperature is
over 140 °F
(60 °C).
Poor battery
compartment
ventilation.
Stop charging if necessary.
Check cable connections.
Check battery voltage/current
and temperature. If battery is
not accepting charge, it may
need to be replaced.
Check for excessive ambient
temperature and adequate
ventilation in the battery
compartment.
Automatic BTS may be
damaged.
If the unit displays a
temperature of over 212 °F
(100 °C), the BTS will need to
be replaced.