Installation Guide
Table Of Contents
- Conextâ„¢ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Troubleshooting the Conext SW via the SCP
975-0638-01-01 Rev A 5–11
Table 5-4 provides a detailed description of the warning messages and solutions.
If you are unable to resolve the problem after referring to this table, contact
customer service.
F93
Wrong Batt
Temperature
Sensor
Automatic An unknowns BTS
was plugged into
the BTS port.
Use only the BTS that was
provided with the Conext SW
Inverter/Charger. To order,
use product number 808-
0232-02.
Table 5-3 Fault Detection Messages
Code Message Type Cause Solution
Table 5-4 Warning Messages
Code Message Fault Type Cause Solution
W48
DC under voltage
(Warning)
Automatic Voltage at the DC
input terminals is
below the Low
Battery Cut Out
(LBCO) setting.
Check for the correct battery
voltage at the inverter's DC
input terminals.
Check for external DC loads
on the batteries.
Check condition of batteries
and recharge if necessary.
Reduce the Low Battery Cut
Out (LBCO) setting.
Battery bank capacity may
be inadequate for the loads
in the system.
W69
AGS not
connected
Automatic The GenSup Mode
setting is enabled
but there is no
AGS connected in
the Xanbus
network.
Install an AGS on the network
or disable the GenSup Mode
setting.