Installation Guide
Table Of Contents
- Conext™ SW Inverter Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-01 Revision: Rev A Date: 12-2012
- Contact Information www.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Precautions When Working With Batteries
- Regulatory
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Multiple Unit Configuration
- Generator Support
- Basic Protection Features
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Conext SW AC/DC/Ports Side Panel
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- Gen Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Using the Advanced Features
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Specifications
6–4 975-0638-01-01 Rev A
AC Transfer Specifications
NOTE: All transfer specifications are at nominal conditions: ambient temperature
of 77 °F (25 °C), split-phase 120/240 VAC, 60 Hz input, unless otherwise
specified.
Physical Specifications
SW 2524 120/240 SW 4024 120/240
Transfer time—utility to invert < 20 ms
Relay current rating
30 A
a
a.Limited by SCP to 24 A due to CEC/NEC regulatory requirements.
Minimum line-to-neutral AC input
voltage for transfer
95 VAC RMS
Maximum
line-to-neutral
AC input
voltage for transfer
135 VAC RMS
Minimum AC input frequency for transfer
44 Hz
Maximum AC input frequency for transfer
70 Hz
Cooling Fan-cooled, temperature controlled
SW 2524 120/240 SW 4024 120/240
L × W × H
15.2×13.5×7.6 in
(387×343×197 mm)
15.2×13.5×7.6 in
(387×343×197 mm)
Net Weight 62 lbs. (28 kg) 76 lbs. (34.5 kg)
ConextSW-NA-OwnersGuide.book Page 4 Thursday, December 20, 2012 2:00 PM