Conext™ XW Inverter/Charger Conext XW+ 5548 NA Conext XW+ 6848 NA Owner’s Guide www.schneider-electric.
Conext™ XW Inverter/Charger Owner’s Guide www.schneider-electric.
Copyright and Contact Copyright © 2007-2014 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
About This Guide Purpose The purpose of this Owner’s Guide is to provide the information and procedures necessary for configuring, operating, maintaining, and troubleshooting the Schneider Electric Conext XW+ Inverter/Charger. Scope This Guide includes information about monitoring and configuring the Conext XW+ Inverter/Charger. The Guide provides guidelines, detailed setup information, and information about operating and troubleshooting the unit.
About This Guide Chapter 1, “Introduction”, describes the operational features of the Conext XW+ Inverter/Charger. Chapter 2, “Monitoring Operation”, contains information about monitoring Conext XW+ Inverter/Charger operation using the inverter information panel or the Conext System Control Panel. Chapter 3, “Configuration” explains how to navigate through the Conext System Control Panel menus and configure the Conext XW+ Inverter/Charger.
Important Safety Instructions READ AND SAVE THESE INSTRUCTIONS - DO NOT DISCARD This guide contains important safety instructions for the Conext XW+ Inverter/ Charger that must be followed during operation and troubleshooting. Read and keep this Owner’s Guide for future reference. Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it.
Safety NOTICE NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.
Safety Safety Information 1. Before using the inverter, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual. 2. Use of accessories not recommended or sold by the manufacturer may result in a risk of fire, electric shock, or injury to persons. 3. The inverter is designed to be permanently connected to your AC and DC electrical systems.
Safety DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E or CSA Z462. • This equipment must only be installed and serviced by qualified electrical personnel. • Never operate energized with covers removed • Energized from multiple sources.
Safety DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Battery Circuit Breakers must be installed according to the specifications and requirements defined by Schneider Electric.s. • Servicing of batteries must only be performed by qualified personnel knowledgeable about batteries and the required precautions. Keep unqualified personnel away from batteries. • Disconnect the charging source prior to connecting or disconnecting battery terminals.
Safety To reduce the risk of battery explosion, follow these instructions and those published by the battery manufacturer and the manufacturer of the equipment in which the battery is installed. FCC Information to the User This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Contents Important Safety Instructions 1 Introduction Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Performance Highlights - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Distinguishing Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Xanbus™ Network Communications Protocol - - - - - - - - - - -
Contents 3 Configuration Using the Conext System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2 Conext XW+ Setup Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2 Setting the Time and Date - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 Using the Setup Menus - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Contents Inverter Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4 Battery Charger Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–7 Faults and Warnings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–10 Warning Messages - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
xiv
1 Introduction Chapter 1, “Introduction”, describes the operational features of the Conext XW+ Inverter/Charger.
Introduction Features The Conext XW+ is a modular building block sine-wave inverter/charger that can be used for residential and commercial battery based off-grid, grid backup, and grid interactive applications. The Conext XW+ is a self-contained DC to AC inverter, battery charger, and integrated AC transfer switch. It is configurable in a hybrid system to operate with generators and renewable energy sources. These configurations are capable of extending battery based off-grid/backup autonomy.
Operation Available Conext XW+ Accessories Accessory Part Number Conext XW+ Power Distribution Panel 865-1015-01 Conext XW+ Power Distribution Panel (Without AC Breakers) 865-1014-01 Conext XW+ Conduit Box 865-1025-01 Conext XW+ Connection Kit for INV2 INV3 PDP 865-1020-02 Conext System Control Panel 865-1050-01 Conext Automatic Generator Start 865-1060-01 Conext MPPT 60 150 Solar Charge Controller 865-1030-1 Conext MPPT 80 600 Solar Charge Controller 865-1032 Conext ComBox 865-1058 Con
Introduction The Conext XW+ has an internal automatic transfer switch (K1, K2) which allows either AC1 or AC2 to be connected to the inverter input, but not both at the same time (See Figure 1-1, “Connection Points and Major Power Conversion Components of Conext XW+ ” on page 1–4). This allows shared AC energy during charging or to directly pass through from AC1, or AC2, to AC Out.
Operation AC1 ACOUT AC2 Figure 1-3 Charging External Batteries and Supplying AC Out with AC Passthrough from AC1 Grid AC1 ACOUT AC2 Figure 1-4 Charging External Batteries and Supplying AC Out with AC Passthrough from AC2 Generator 975-0240-01-01 1–5
Introduction AC1 ACOUT AC2 Figure 1-5 Converting Excess Available DC power for Export to Utility Grid (AC1) and AC Out AC1 ACOUT AC2 Figure 1-6 AC Pass-through 1–6 975-0240-01-01
Operation Surge Performance Unlike many other inverters, the Conext XW+ helps stop voltage from sagging dramatically during surge conditions. The Conext XW+ handles surges of over twice its rated output power with only a minimal drop in output voltage for limited periods of time. Islanding Protection Islanding protection is an essential safety feature that helps reduce harm to those working on the utility grid from a distributed energy source such as the Conext XW+.
In addition to the information panel, the Conext System Control Panel indicates a utility fault with the Fault light and also displays a fault message on screen (faults F23 to F40 are utility faults—see Figure 4-6, “Fault Messages” on page 4–19). The fault cannot be manually cleared. Utility faults will clear automatically when the utility grid voltage and frequency return to within the ranges programmed into the Conext XW+.
Operation Consult the manufacturer's specifications to determine if your PV inverter is compatible with Active Frequency Shift Power Curtailment. Conext XW+ AC coupling function is enabled by default (Advanced Features Menu). NOTICE AC COUPLED PV INVERTER COMPATIBILITY AC power generated by AC coupling PV inverters with Conext XW+ must be consumed by AC loads or used to charge batteries. As an alternative, the excess power produced from a PV inverter can be routed to dump loads.
Introduction Parallel Charging Multiple Conext XW+ units on the same Xanbus network synchronize their charging stages to help provide efficient charging of the battery bank. When a single unit transitions from bulk to absorption, so do all other units. In absorption, all units must complete the absorption stage before any of them transition to the next stage. Note that units stop sharing charge current just before completing the bulk stage and only share charging load during the bulk stage.
Operation Auxiliary Output Each Conext XW+ has one programmable 12 V, 0.25 A auxiliary output that is able to run a small fan or operate an external relay to perform other functions. Examples include remotely starting a two-wire start generator in cases where the Xanbus-enabled Conext AGS is not used, disconnecting external non-critical loads, or turning on a diversion load for battery voltage regulation. See “Auxiliary Output Settings” on page 3– 34 for programme parameters.
Introduction Monitoring the Conext XW+ Operation of the Conext XW+ can be monitored using the factory-installed inverter information panel or the optional Conext System Control Panel and ComBox. To configure the Conext XW+, the Conext System Control Panel or ComBox must be used. Conext XW+ Information Panel The Conext XW+ information panel features: • Buttons for Conext XW+ Startup/Shutdown/Standby control, clearing faults and warnings, and battery equalization.
Monitoring the Conext XW+ Conext System Control Panel The Conext System Control Panel (Conext SCP) or Conext ComBox is required for configuring the Conext XW+ and other Xanbus-enabled system components. The Conext SCP features: • A liquid crystal display which provides graphics and text describing real time operation and status information. • LED event and warning indicator. • Internal clock which is used to control time-dependent Conext XW+ functions.
Introduction 1–14 975-0240-01-01
2 Monitoring Operation Chapter 2, “Monitoring Operation”, contains information about monitoring Conext XW+ Inverter/Charger operation using the inverter information panel or the Conext System Control Panel.
Monitoring Operation Monitoring Operation with the Inverter Information Panel The inverter information panel on each Conext XW+ monitors a single Conext XW+. The Conext XW+ information panel displays basic information and performs start up, shut down, equalization and standby functions. LEDs on the information panel indicate AC input status, Conext XW+ status, battery condition, and charging and equalization status.
Monitoring Operation with the Inverter Information Panel When one AC input LED is on and the other AC input LED is flashing, AC input is present on both AC1 and AC2. However, the Conext XW+ can qualify and receive AC input from only one source at a time. The qualified source is represented by the steadily lit LED. When two sources of AC input are present, the Conext XW+ uses the source selected under AC Priority in the AC Settings menu.
Monitoring Operation Monitoring Charger Status The green LED labelled “A” indicates the Conext XW+ is charging the battery bank. When this LED is on, the numeric display screen shows battery charging current in amps. Symbol LED On LED Flashing LED Off The Conext XW+ is charging the battery bank. The numeric display screen shows battery charging current in amps. AC coupled charging is occurringa. The Conext XW+ is not in charge mode.
Monitoring Operation with the Inverter Information Panel Symbol LED On LED Flashing The Conext XW+ has a fault and has stopped charging or inverting. The LED also turns on steadily if the unit has both a fault and a warning. The Conext XW+ has a warning. A warning may escalate to a fault if the warning condition does not go away. Equalizing Batteries Button Pressing the Equalize button ( symbol) for five seconds initiates a battery equalization cycle.
Monitoring Operation Note: In a system where more than one device is capable of equalizing batteries (such as a system including multiple Conext XW+ units and/or Conext Solar Charge Controllers), there is no system-wide equalization command for all devices. To equalize with multiple devices, each would have to be enabled individually. Alternatively, equalization can be performed using only the selected device.
Monitoring Operation with the Inverter Information Panel If the STARTUP/SHUTDOWN button is pressed and held on a Conext XW+ and a Conext AGS is installed in the system, the unit stops inverting or charging immediately and shuts down completely in 120 seconds. During this time, the display shows OFF. This interval allows the Conext AGS to stop the generator after a cool down period.
Monitoring Operation Figure 2-3 Battery Level LEDs Reading the Display Screen The numeric display screen shows the following information about the operational state of the Conext XW+: 2–8 • Output power in kilowatts (when the (kW) LED is lit). • Battery charger current in Amps (when the • Stb when the Conext XW+ is in Standby mode. • Sch when the Conext XW+ is in Search mode. See “Using Search Mode” on page 3–9. • OFF when the STARTUP/SHUTDOWN button is pressed and held for five seconds.
Monitoring Operation with the Conext SCP Monitoring Operation with the Conext SCP The Conext System Control Panel (Conext SCP) provides remote configuration and monitoring capability for the Conext XW+ and all other Xanbus-enabled devices in the network. You can monitor Conext XW+ operation on the Conext SCP using the: • System Status screen (see page 2–13) • Conext XW+ Home screen (see page 2–13) • Conext XW+ Meters Menu (see page 2–16).
Monitoring Operation Using the Standby Button The Standby button has two functions. The Standby button can disable inverting and charging for the Conext XW+ units in the system or when pressed simultaneously with the Exit button, can put the entire system into Standby mode. Pressing the Standby button produces the same result as disabling Invert and AC Charge in the System Settings menu.
Monitoring Operation with the Conext SCP Appears for a few seconds after the system starts up or when the system has been reset. Startup Screen System Status System Status Screen Select Device Press Enter to view Select Device menu. Select Device Screen Select device from list and press Enter to view Device Setup menu. XW+ 6848:Home Conext XW Home Screen Device 2:Home Device 2 Home Screen Press Enter from a Device Home screen to view the Device Setup menu.
Monitoring Operation XW+ Inverter/Chargers, two Conext Solar Charge Controllers, one Conext AGS module, and one Conext SCP connected to a single battery bank, a single generator, and a common utility grid. The System Status screen features a Menu arrow pointing to the Enter button. Pressing Enter takes you to the Select Device menu. For more information, see “Reading the System Status Screen” on page 2–13.
Monitoring Operation with the Conext SCP Select Device menu Conext XW+ Setup menu Select Device XW+ 6848 00: Setup Meters XW+ 6848 Select device from list and press Enter to view Device Setup menu [Enabled] [Disabled] [Disabled] [Enabled] [Bulk] [Disabled] [Operating] Figure 2-5 Selecting a Device Setup Menu Reading the System Status Screen The System Status screen displays: • Qualified AC source (if applicable) and total power to and from the source. • Battery voltage and capacity level.
Monitoring Operation Top Line: Device name and number XW+ 6848 00:Home -26.4A setup 0.0V Invert 51.9V 1250W 0W Line 1: Conext XW+ status Line 2: Battery current (in + or out -) and voltage (Battery current is negative when selling. Amps * Volts = Total Power Sold) system Line 3: Power supplied to loads Line 4: AC in status Setup arrow indicates the Enter button. System arrow indicates the Exit Pressing Enter displays the Conext XW+ button. Pressing Exit displays the setup menu. System Home screen.
Monitoring Operation with the Conext SCP Table 2-1 Conext XW+ Home Screen States Conext XW+ Status Displayed When... Float The Conext XW+ is float charging the batteries from qualified AC input from the utility grid (AC1) or a generator (AC2). The Conext XW+ is set for three-stage charging. AC input is also passed through to the load while float charging. CHG Finish The Conext XW+ has completed charging or the charge cycle has been interrupted and is transitioning to the next state.
Monitoring Operation Table 2-1 Conext XW+ Home Screen States Conext XW+ Status Load Shaving Displayed When... The Conext XW+ supports the utility grid when there is AC input on AC1 and the current required to power the loads rises above the Load Shave Amps setting between the Load Shave Start and Load Shave Stop times set on the Grid Support menu.
Monitoring Operation with the Conext SCP XW+ 6848 00: Setup Meters XW+ 6848 00: Meters [Enabled] [Disabled] [Disabled] [Enabled] [Bulk] [Disabled] [Operating] 4500VA 3200W 21.1A 120V 21.1A 120V 60Hz 0VA 0W 0.0A 0V 0.0A 0V 0Hz 4500VA 3200W 21.1A 120V 21.1A 120V 60Hz Float 3.7A 57.
Monitoring Operation Table 2-2 Meters Screen Screen Item Description AC1 AC input power connected to the Conext XW+ AC1 terminals, in volt-amps and watts. AC1 is assumed to be connected to the utility grid, but can be connected to any other AC source. AC1 in L1 AC input voltage and current connected to the Conext XW+ AC1 L1 terminals. This input voltage display may drift slightly before the Conext XW+ has synchronized to the grid.
3 Configuration Chapter 3, “Configuration” explains how to navigate through the Conext System Control Panel menus and configure the Conext XW+ Inverter/Charger.
Configuration Using the Conext System Control Panel The Conext XW+ is configured using the Conext SCP (Conext System Control Panel). The Conext SCP provides access to settings relating to AC input and output, battery charging, and grid-tie operation. Conext XW+ Setup Menu The Conext XW+ Setup menu is accessible either from the system Home screen or from the Conext XW+ Home screen. To navigate to the Conext XW+ Setup menu: 1. From the system Home screen, press Enter to view the Select Device menu.
Using the Conext System Control Panel Table 3-1 Conext XW+ Setup Menu Menu Item Description Grid Support Enables or disables grid-interactive Conext XW+ features, such as grid support and grid sell mode. See “Grid Support Settings” on page 3–23. To allow grid support to function after battery charging has completed, it is recommended to set the Charge Cycle to 2-Stage. The MPPT controllers must still be set to 3stage. See “Charger Settings Menu” on page 3–11.
Configuration Note: Network time on the ComBox overrides time configured on any individual device in the network-enabled power system using network time protocol (NTP). If your device is not compatible with NTP, Conext XW+ features such as peak load shaving and charger block may not work correctly, and charge controller daily power production values may reset at an unexpected time. If your device is working incorrectly, configure the ComBox to use the local time and date.
Using the Setup Menus • Inverter settings (see page 3–8) • Charger settings (see page 3–11) • AC transfer limit settings (see page 3–22) • Grid support and peak load shaving settings (see page 3–23) • Generator support settings (see page 3–32) • Auxiliary output settings (see page 3–34). • Multi-unit operation, including customizing the default model name of the Conext XW+ and setting its network device number.
Configuration Note: If you have no more settings to change, it is recommended to leave the Setup menu in the basic settings format to help prevent unintended configuration. If the Setup menu displays Advanced Settings, press Enter + up arrow + down arrow at the same time. The Setup menu should then display Basic Settings as the last item on the menu.
Using the Setup Menus Basic Settings XW+ 6848 00:Basic Batt Type [Flooded] XW+ 6848 00:Inv [46V] [10s] [70V] [50W] [2s] [440Ah] [100%] [2-Stage] [50V] [AC1] [60A] [60A] [54V] [44V] XW+ 6848 00:Chg [Flooded] Custom Settings [440Ah] [100%] [2-Stage] [Warm] [50V] [180min] [12:00AM] [12:00AM] XW+ 6848 00:AC [AC1] [60A] [106V] [132V] [55Hz] [65Hz] [60A] [80V] [138V] [55Hz] [65Hz] Advanced Settings XW+ 6848 00: Adv [XW6048 01] [Enabled] [64.0V] [57.6V] [57.6V] [54.
Configuration Inverter Settings Menu The Inverter Settings menu contains settings that control when the Conext XW+ starts and stops producing AC output. Table 3-2 Inverter Settings Menu Item Description Low Batt Cut Out Low Batt Cut Out controls when the inverter stops producing AC output due to a low battery voltage condition. The inverter will stop producing AC output only after this level has been reached for the period of time set by the LBCO Delay. This setting is not temperature compensated.
Inverter Settings Menu Using the Low Battery Cut Out and LBCO Delay Settings WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel.
Configuration Single units When a single Conext XW+ has search mode enabled, the inverter sends electrical search pulses through its AC output. These search pulses look for connected AC loads. The delay between search pulses is set using the Search Delay setting. After a load larger than the Search Watts setting is detected, the inverter starts producing AC output.
Charger Settings Menu Charger Settings Menu The Charger Settings menu provides options for configuring the Conext XW+ to operate from your battery bank. Table 3-3 Charger Settings Menu Item Description Batt Type Sets the system battery chemistry and type: Flooded (default), AGM, Gel, Lithium Ion, and Custom. Selecting Custom displays the Custom Settings item, which allows you to adjust the settings for each charging stage.
Configuration For default settings, see “Charger Menu” on page B–3. Battery Charger Functions When AC power is available, the Conext XW+ can operate as a battery charger. Different battery types and chemistries require different charging voltage levels. Not charging batteries at the required levels can shorten battery life or damage the batteries. The Conext XW+ is configured at the factory to work with the battery types recommended for inverter applications.
Charger Settings Menu Notes: When the charge cycle is interrupted, the charger will restart charging at the beginning of the multi-stage algorithm. Exit Current Threshold can be effectively disabled by programming the amp-hour capacity to 0. In this case, absorption will only exit once the Max Absorption timer expires. Charge current during equalize state (optional state not shown here) is normally limited to 10% of the programmed amp-hour capacity setting.
Configuration Note: If there are DC loads on the batteries, the charger’s current may not decrease to a level to transition to the next stage of charging. In this case, the charger stays in absorption until the Absorb Time setting is reached. To avoid having the charger remain in absorption for too long, adjust Absorb Time on the Charger Settings menu.
Charger Settings Menu Float Stage Float charge maintains the batteries slightly above the self discharge voltage of the batteries. The charge current in float is the current necessary to maintain the batteries at the Float Voltage setting, limited only by the inverter's capability or other settings that limit the inverter's maximum charge rate. Float charging reduces battery gassing, minimizes watering requirements (for flooded batteries), and helps the batteries remain in a constant state of readiness.
Configuration Bulk Stage Battery Voltage Absorption Stage (Boost Stage) Absorption Voltage 2-Stage Charge Custom Charge Recharge Voltage Return to Bulk Stage Boost Timer 1hr fixed Time Max Absorb Time - Dflt 3 hrs (adjustable 1 min - 8 hrs ) Battery Current Max Charge Rate Absorption Exit Current Threshold = 2% of programmed AH capacity Time Figure 3-5 Two-Stage Charging Cycle 3–16 975-0240-01-01
Charger Settings Menu Note: When the charge cycle is interrupted, the charger will restart charging at the beginning of the multi-stage algorithm. Exit Current Threshold can be effectively disabled by programming the amp-hour capacity to 0. In this case, absorption will only exit once the Max Absorption timer expires. Charge current during equalize state (optional state not shown in graph) is normally limited to 10% of the programmed amp-hour capacity setting.
Configuration After absorption, the maximum charge DC current is set to 10% of battery capacity (for example, 44 A for 440 Ah). See Figure 3-6. This constant current charge will continue until the voltage has increased to the equalize voltage at which point the battery will be regulated at the temperature compensated equalize voltage.
Charger Settings Menu If the Conext XW+ will not perform the equalization, see Warning W96 “Cannot Equalize” in Table 4-3 on page 4–12. WARNING EQUALIZATION HAZARD Only flooded lead acid batteries should be equalize charged. Hydrogen and oxygen gases are produced when batteries are equalized and can potentially cause an explosion if ignited. Corrosive battery acid can escape.
Configuration Custom Battery Settings Menu NOTICE BATTERY TYPE AND SETUP HAZARD To avoid damaging your batteries during charging or equalization, consult your battery manufacturer and associated documentation before setting a custom battery type. Failure to follow these instructions can result in equipment damage. WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only.
Charger Settings Menu Table 3-4 Custom Battery Settings Menu Item Description Batt Temp Comp Battery temperature compensation for a custom battery type. This setting is the reference that the BTS uses to adjust the charging voltage when the temperature is above or below 25 °C (77 °F).
Configuration AC Input Settings WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel. Failure to follow these instructions can result in death or serious injury.
Grid Support Settings Table 3-5 AC Settings Menu Item Description AC1 Breaker Sets the AC1 (Grid) breaker size, based on the size of the breaker installed upstream from the AC1 connection port. The installed breaker size must not exceed the capacity of the upstream distribution panel. The Conext XW+ limits the maximum current draw on AC1 by derating its charging current to an equivalent of 80% of the AC1 breaker setting.
Configuration Note: Grid support and sell functions are modes of operation that are subject to local and/or national grid interconnection requirements in most jurisdictions. It is the responsibility of the installer and system operator to ensure that all applicable procedures and technical requirements are complied with before turning on either of these modes. Note: Upon startup, the Conext XW+ does not enable grid support functions for five minutes (300 seconds).
Grid Support Settings Table 3-6 Grid Support Settings Menu Item Description Grid Supp Volts Sets the level to which the batteries will be discharged when the inverter is selling power to the grid or supporting the power grid by providing additional power to the loads on AC Out. This setting is not adjusted for the battery temperature even if the temperature sensor is installed. Sell Turns sell mode on and off.
Configuration Table 3-6 Grid Support Settings Menu Item Description Load Shave Amps Sets the maximum amount of current that can be drawn from the AC1 (grid) input by the loads and battery charger combined. This setting determines the amperage level at which the inverter starts drawing power from the batteries to add to the utility power to meet the demand of the loads.
Prioritizing and Managing Energy Sources with Advanced Features Prioritizing and Managing Energy Sources with Advanced Features The Conext XW+ can be programmed to control how and when to use utility power as well as external DC sources of energy such as batteries and solar charge controllers. Advanced features allow management of peak loads, time-ofuse billing and self consumption. Grid Support WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only.
Configuration Grid Support enabled, Sell enabled In this mode, all available excess DC power is first used to power local AC loads attached to the inverter output. Any remaining power (up to the Max Sell Amps setting) is exported to the utility grid (AC1). A battery bank rated at least 440 Ah is recommended for best sell performance. Sell Block The sell block feature halts the export of energy to the grid connected to AC1 for a period of time each day.
Prioritizing and Managing Energy Sources with Advanced Features In an enhanced grid support set up the Conext XW+ automatically tracks the Conext MPPT Solar Charge Controller voltage as it transitions through charge states (from bulk to absorption to float). This allows the system to execute a complete battery charge cycle while still converting excess DC power to AC power to support the AC loads or be exported to the utility grid.
Configuration electricity, it is preferable to use utility power for charging only during non-peak hours. Charger block can prevent utility power from being used for battery charging during peak billing periods. During the time period set between Chg Block Start and Chg Block Stop, AC1 (Grid) input continues to be passed through to the loads. Inverter operation remains unaffected during the charger block period.
Prioritizing and Managing Energy Sources with Advanced Features When the Time in Float is different than zero, PLS shall start only if the battery amperage remained at the specified level for the configured time. Example: Load Shave=Enabled, LoadShaveAmps=10 A, LoadShaveStart=6:00pm, LoadShaveStart=9:00pm, Time in Float=60 min, PLS Dly 2h= Enabled.
Configuration Generator Support Settings WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel. Failure to follow these instructions can result in death or serious injury.
Generator Support Settings Gen Support Mode Battery Voltage V[DC max] Gen support mode V[LBCOmin] AC In Current > GenSupportA [entry] 40V AC In Current < GenSupportA [exit] [A] Figure 3-9 Gen Support Mode Graph Table 3-7 Gen Support Menu Values Setting Description GenSupp Mode Turns the generator support feature on and off. GenSupp Amps Sets the generator load level at which the Conext XW+ begins to convert external DC energy and supply additional AC power in parallel to loads on AC Out.
Configuration Auxiliary Output Settings WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel. Failure to follow these instructions can result in death or serious injury.
Auxiliary Output Settings Table 3-8 Aux Menu Values Setting Description Clear Delay Sets a delay period between when the Clear Level setting occurs and when the auxiliary output becomes inactive. Charge Bulk Exit Exits charge bulk mode. In charge bulk mode, the XW operates as a constant power source to the battery bank. Charge Absorption Exit Exits charge absorption mode and starts the following mode, depending on whether the unit is set to two or three-stage charge.
Configuration Clear Delay time. Battery temperature is measured with a battery temperature sensor. Do not use this setting if a battery temperature sensor is not installed. With this setting, the auxiliary output can turn on a fan to vent the battery compartment. Fault Activates the auxiliary output when a fault occurs. The auxiliary output clears when the fault is cleared. State of Charge (SoC) This feature works in conjunction with the Conext Battery Monitor.
Multi-Unit Config Menu Multi-Unit Config Menu WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel. Failure to follow these instructions can result in death or serious injury.
Configuration Table 3-9 Multi-Unit Config Menu Item Description Default Range Inverter Mode For a split-phase system: For a multi-unit system to operate, one Conext XW+ must be configured to SplitPhMaster and the rest as SplitPhSlave, otherwise a system-wide fault is asserted.
Multi-Unit Config Menu Setting the Device Name The Dev Name setting allows you to customize the name of the Conext XW+ as it is displayed on other screens and menus. The characters available are: • • • • A to Z a to z 0 to 9 space Note: Increasing the number of characters in a device name may cause other text on the same line to run off the edge of the screen. Device names should be limited to 10 characters or less. To customize the Conext XW+ name: 1. On the device setup menu, select Advanced Settings.
Configuration Setting the Device Number When several devices of the same type are installed in the Xanbus network, setting the device number is required to give a Xanbus-enabled device a unique identity. When each identical device has a unique number, the Conext SCP can correctly identify and display status information for each device. A device number consists of two digits ranging from 00 (default) to 31.
Multi-Unit Config Menu Three-Phase Configuration WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel. Failure to follow these instructions can result in death or serious injury.
Configuration Note: The XanBus communications protocol supports a maximum of twelve Conext XW+ units in a single network. To set up a three-phase system: 1. Follow the instructions in the Conext XW+ Inverter/Charger Installation Guide to Daisy chain XW-phA, XW-phB, and XW-phC at each unit’s AC sync port and connect an AC sync cable between the second AC sync port in unit 2 and an AC sync port in unit 3. 2.
Connections Menu Table 3-10 Example Three-phase Inverter Assignments Line or Phase Inverter Mode Role Assignmenta Suggested Device Number 3Ph L2 Slave Phase-B or Line-2 Slave 21 Line-3 or Phase-C 3Ph L3 Master 3Ph L3 Slave Phase-C or Line-3 Master 30 Phase-C or Line-3 Slave 31 a.Each phase can support one master unit and one slave unit. b.The L1 Master is also the master Conext XW+ for the entire system.
Configuration Table 3-11 Connections Menu Item Description DCConn DC input and output connection. This is the common DC connection shared between the Conext XW+, charge controllers, and referenced by the Conext Automatic Generator Start. ACOut AC output connection. This connection specifies a common AC output connection shared between Conext XW+ units. The AC output connection has to be configured so that the units know if they are connected to the same load or not.
Copying Settings From Another Unit Copying Settings From Another Unit WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel.
Configuration Resetting the Conext XW+ to Default Settings WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel. Failure to follow these instructions can result in death or serious injury.
Using the Advanced Features Using the Advanced Features WARNING ADVANCED CONFIGURATION HAZARD Advanced menu settings should be used by qualified personnel only. Three phase operation should be configured by qualified personnel only. Consult with the local utility before enabling Conext XW+ sell mode or grid support functions. Do not change these settings unless you are under the supervision and direction of qualified personnel. Failure to follow these instructions can result in death or serious injury.
Configuration Table 3-12 Advanced Features Menu Item Description AC_Coupling AC Coupling function is enabled by default (Advanced Features Menu) and should remain enabled except in cases where the DC voltage level is allowed to have large variations and the AC line frequency needs to remain constant. Batt_Balance The Battery Balance function is disabled by default and is intended for use with inverters drawing power from a single battery bank.
4 Troubleshooting Chapter 4, “Troubleshooting”, contains information and procedures for identifying and solving possible problems with the Conext XW+ Inverter/Charger.
Troubleshooting General Troubleshooting Guidelines This section will help you narrow down the source of any problem you may encounter. Please read the following troubleshooting steps: 1. Check for a Warning or Fault message on the Conext System Control Panel or a Fault code on the inverter information panel. If a message is displayed, record it immediately. 2. As soon as possible, create a detailed record of the conditions at the time the problem occurred.
Inverter Applications Inverter Applications The Conext XW+ performs differently depending on the AC loads connected to it. If you are having problems with any of your loads, read this section. Resistive Loads Resistive loads are the easiest and most efficient to drive. Voltage and current are in phase, which means they are in step with one another. Resistive loads generate heat in order to accomplish their tasks. Toasters, coffee pots, and incandescent lights are typical resistive loads.
Troubleshooting Clocks You may notice that your clocks are not accurate. Some of the clocks on your appliances may reset when the Conext XW+ is in search mode. Disabling search mode will resolve this issue (See “Using Search Mode” on page 3–9). Searching When the inverter is in search mode, it may fail to start some loads even though the rated wattage on the load is more than the Search Watts setting. Disable search or apply an additional load (companion load) to make the inverter exit search mode.
Inverter Troubleshooting Problem Possible cause Solution(s) No AC power output. Open AC output breakers or fuses and bad output wire connections. Check the Load AC Voltage status on the SCP Meters screen and check AC voltage on the inverter AC Out terminal block. The inverter information panel displays Sch. Inverter is disabled. Re-enable inverter.
Troubleshooting Problem Possible cause Solution(s) Inverter goes into invert mode and starts producing AC output and then stops or does not start at all. Search Watts setting is too low or high. Potential problem loads for search mode: If the search sensitivity is set higher than the combined loads, then connect an auxiliary load to bring the inverter out of search mode before the appliances can be turned on.
Battery Charger Troubleshooting Battery Charger Troubleshooting To determine the cause of a charger error condition, refer to the troubleshooting solutions below to resolve the situation. Problem Possible Cause Solution AC1/AC2 LED is on, but will not start charging (allow 40 seconds to synchronize). 1) Charger is disabled on the Setup menu. 1) Enable the charger. 2) Charger Block is enabled and the Conext XW+ is inside of the charger block time window.
Troubleshooting Problem Possible Cause AC1 or AC2 LED is flashing, but will not start charging AC voltage and frequency at the AC input terminal are within nominal range, but the inverter output is not yet synchronized to the AC source. There are four possible causes: (allow 40 seconds to synchronize). 4–8 Solution 1) The inverter may already be synchronized to another AC source. 1) The inverter is operating normally.
Battery Charger Troubleshooting Problem Possible Cause Solution Charger amperage drops off before full charging has finished (no Fault LED). AC frequency at the AC input terminal may be out-of-tolerance (too high or low) or the AC voltage may be outside the Hi AC Volt or Lo AC Volt settings. AC input voltage approaching the low disconnect level. Check the settings on the AC Settings menu. Check for the correct AC voltage or frequency at the AC input terminal.
Troubleshooting Problem Possible Cause Solution Charger output is low. Loose or corroded battery connections. Check and clean all connections. Loose AC input connections. Check and tighten AC wiring connections. Worn out batteries. Replace batteries. Battery cables too small or too long. Refer to cable and battery recommendations in the Conext XW+ Installation Guide. If a BTS (Battery Temperature Sensor) is installed, it may be in a cold area or have fallen off the batteries. Inspect the BTS.
Faults and Warnings Warning Messages Warning messages appear on the Conext SCP to alert you to an impending system change. You can view the 20 most recent warning messages using the Conext SCP’s warning log, accessible from the View Device Info menu. Each warning has a time stamp to let you know the date and time that the warning appeared. If several warning messages occur before you can acknowledge or clear them, they are displayed together on a warning list.
Troubleshooting Table 4-2 Warning Types and Behavior Warning type Behavior Manual warning Require you to acknowledge them before you can proceed with configuring or operating the Conext XW+. Manual warnings are usually in the form of a Yes/No question that you may acknowledge by pressing the Enter button on the Conext SCP for Yes and the Exit button for No. Refer to the Conext System Control Panel Owner’s Guide for more information. Table 4-3 provides descriptions of the warning messages and solutions.
Faults and Warnings Table 4-3 Warning Messages Conext System Warning Control Panel Number Message W57 FET1 Over Temperature Warning Type Cause Solution Automatic Internal temperature is over 85 °C (185 °F). AC input voltage may be too high while charging. Check for high input AC voltage. Operating too large of a load for too long while inverting. Remove excessive loads. Ambient temperature may Let inverter cool down and try restarting. be high. Inverter cooling fan may have failed.
Troubleshooting Table 4-3 Warning Messages Conext System Warning Control Panel Number Message W70 Synchronization Warning Warning Type Cause Solution Manual, AC input is not qualified 1. An AC input voltage phase is lost or out of the AC range in the three-phase. 1. Check the AC voltage presence of each phase at the AC input terminals for each Conext XW+. 2. AC input voltage phases are not synchronized with Conext 3-phase system. 2.
Faults and Warnings Table 4-3 Warning Messages Conext System Warning Control Panel Number Message Warning Type W501 Manual Inv/Chg is trying to fix a memory problem 975-0240-01-01 Cause Solution Non-volatile memory warning Normal operation may return or may go to fault. Turn Conext XW+ off and on to resume normal operation.
Troubleshooting Fault Messages When the Conext XW+ detects a fault condition, the fault is displayed on the Conext System Control Panel. The Conext XW+ also illuminates the Fault light on the Conext System Control Panel and inverter information panel. A fault affects the operation of the unit. See “Fault Types” on page 4–17 for an explanation of the different fault types.
Faults and Warnings Fault Types There are three types of fault messages: automatic faults, manual faults, and escalating automatic faults. Table 4-4 describes how they differ in their behavior and how you can respond to them when they appear on the Conext System Control Panel. Table 4-4 Fault Types and Behaviors Fault type Behavior Automatic faults Clear automatically if the fault condition that generated the message goes away.
Troubleshooting Table 4-5 Inverter Operation After Faults Faults State when Faults Occur Action After Faults F23 to F40: Anti-Islanding Grid Support (Peak Load Shaving or Selling) Unit moves to AC bypass and waits for nominal grid conditions to return for a minimum of five minutes. F41, F42: Aux power supply voltage Unit has qualified AC input. Unit shuts down and waits for nominal AC output voltage level, or a manual clear from user. F44: Battery Over Temp Any state.
Faults and Warnings Table 4-6 Fault Messages Fault Number Message Fault Type Cause Solution F1 AC Output Under Voltage Escalating Auto Fault. Must occur 3 times in 2 minutes before becoming a manual fault. AC under voltage shutdown at 108 V. The inverter has shut down to protect the loads. Clear the fault and attempt restart. If problem persists, call customer service. F2 AC Output Over Voltage Escalating Auto Fault. Must occur 3 times in 30 seconds before becoming a manual fault.
Troubleshooting Table 4-6 Fault Messages Fault Number Message Fault Type Cause Solution F23 AI Over Frequency Automatic Over-frequency antiislanding, caught by the AC qualification limit. No action required. The inverter stops selling and disconnects from the grid. When the fault clears, a five-minute timer begins counting down. The inverter does not sell again until grid voltage and frequency are within range for five minutes.
Faults and Warnings Table 4-6 Fault Messages Fault Number Message Fault Type Cause Solution F35 AI L2 Under Voltage Automatic See F34. See F23. F36 AI L1L2 Under Voltage Automatic See F34. See F23. F37 AI L1 Under Voltage Automatic Under-voltage antiislanding, fast disconnect, 66 VAC. See F23. F38 AI L2 Under Voltage Automatic See F37. See F23.
Troubleshooting Table 4-6 Fault Messages Fault Number Message Fault Type Cause Solution F44 Automatic Battery over- temperature shutdown at 60 °C. Clear the fault and attempt restart. Stop charging, check battery voltage and temperature. Check for excessive ambient temperature and adequate ventilation in the battery compartment. Battery Over Temperature Note: Shutdown temperature is above 60 °C. Recovery occurs at 50 °C where the XW will be enabled again.
Faults and Warnings Table 4-6 Fault Messages Fault Number Message Fault Type F52 EEPROM Error Manual No action. Clear fault and resume operating or configuring the unit. If the fault persists, have the unit serviced. F53 EEPROM Error Manual See F52. F54 EEPROM Error Manual See F52. F55 EEPROM Error Manual See F52. F56 EEPROM Error Manual See F52. F57 FET1 Over Temperature Shutdown Automatic 975-0240-01-01 Cause Solution Internal temperature is over 105 °C.
Troubleshooting Table 4-6 Fault Messages Fault Number Message Fault Type Cause Solution F58 FET2 Over Temperature Shutdown Automatic See F57. See F57. F59 GOCFG process failed Manual Auto-configuration process failed. Retry the “Copy From” procedure, or configure the unit manually. F63 AC Overload Escalating Auto Fault. Must occur 3 times in 5 minutes before becoming a manual fault. Excessive load on the AC output. Check for loads above the inverter’s capacity.
Faults and Warnings Table 4-6 Fault Messages Fault Number Message Fault Type Cause Solution F68 Transformer Over Temperature Automatic The transformer temperature is over 140 °C. The fault clears when the transformer temperature falls to 125 °C. Ensure adequate ventilation around the Conext XW+. Reduce AC loads. F69 External Sync Failed Manual F70 Check Phase Configuration Automatic Check connections and cable on external AC sync port.
Troubleshooting 4–26 975-0240-01-01
A Specifications Appendix A, “Specifications” provides the electrical and mechanical specifications for the Conext XW+ Inverter/Charger.
Specifications Electrical Specifications Table A-1 Conext XW+ Inverter/Charger Electrical Specifications Conext XW+ 6848 NA Conext XW+ 5548 NA Continuous Output Power 6,800 W 5,500 W Surge Rating (Overload for 1 minute) 12,000 W 9,500 W Surge Rating (Overload for 5 minutes) 11,000 W 9,000 W Surge Rating (Overload for 30 minutes) 8,500 W 7,000 W Surge Current L-N: 104 Arms (60 s) L-L: 52 Arms (60 s) L-N: 82 Arms (60 s) L-L: 41 Arms (60 s) Waveform True Sine Wave Idle Consumption—Inverter
Electrical Specifications Table A-1 Conext XW+ Inverter/Charger Electrical Specifications Conext XW+ 6848 NA Power Factor Corrected Charging Conext XW+ 5548 NA PF (0.98) Typical Transfer Time 8 ms a.Automatically adjusts when entering Sell Mode. This unit or system is provided with fixed trip limits and shall not be aggregated above 30 kW on a single Point of Common Connection. b.Conext XW+ 6848 NA (Part Number 865-6848-01) c.
Specifications Conext XW+ 5548 UL L1-N or L2-N: Imbalanced Line Loading 9500 Line-Neutral (120 V) Load [W] Surge Power Versus Time 9000 5 Minutes 5200 30 Minutes 4200 0 10 1 10 2 10 3 10 Time in Seconds 4 10 5 6 10 10 Conext XW+ 6848 UL L-L Inverter Surge Profile 12500 Surge Power Versus Time 5 Minutes Line-Line (240 V) Load [W] 11000 30 Minutes 8500 7000 4200 0 10 A–4 1 10 2 10 3 10 Time in Seconds 4 10 5 10 6 10 975-0240-01-01
Electrical Specifications Conext XW+ 6848 UL L1-N or L2-N: Imbalanced Line Loading 12000 L1/L2-Neutral (120 V) Load [W] Surge Power Versus Time 5 Minutes 8800 30 Minutes 6300 4800 0 10 1 10 2 10 3 10 Time in Seconds 4 10 5 10 6 10 Figure A-1 Conext XW+ AC Overload Capability Output Power Versus Ambient Temperature Note: For the Conext XW+ 6848 model, the power can be limited by the installed DC and AC breakers.
Specifications XW+ Series Power derating 8000 7000 XW+ 6848 6000 Output Power (Watts) XW+ 5548 5000 4000 3000 2000 1000 0 -25 -15 -5 5 15 25 35 45 55 65 75 Ambient Temperature (°C) Figure A-2 Output Power Versus Ambient Temperature A–6 975-0240-01-01
Electrical Specifications Conext XW+ Efficiency Inverting Efficiency (Typical) 100% 95% XW+ 6848 Efficiency (%) 90% XW+ 5548 85% 80% 75% 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 Output Power (Watts) Figure A-3 Inverting Efficiency (Typical) 975-0240-01-01 A–7
Specifications Charging Efficiency (Typical) 100% Efficiency (%) 95% 90% XW+ 5548 85% XW+ 6848 80% 75% 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 Charge Current (Amps) Figure A-4 Charging Efficiency (Typical) A–8 975-0240-01-01
Electrical Specifications Charging Efficiency Power Factor XW+ 6848 100% XW+ 5548 AC Input Current (Amps) Power Factor (%) 95% 90% 85% 80% 75% 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 Battery Current (Amps) Figure A-5 Charging Efficiency (Power Factor) 975-0240-01-01 A–9
Specifications Mechanical Specifications Table A-2 Conext XW+ Inverter/Charger Mechanical Specifications Model Supported Battery Types Conext XW+ 6848 NA Conext XW+ 5548 NA Flooded (default), Gel, AGM, Lithium Ion, Custom Battery bank size 440–10000 Ah Non-Volatile Memory Yes Inverter Information Panel Status LEDs indicate AC In status, faults/warnings, equalize mode, battery level. 3-character display indicates output power or charge current, fault/warning codes.
Accessories Internal Transfer Relay L1-Gen N Control & Monitoring L2-Gen L1-Grid N L2-Grid DC+ AC EMI Filter AC Filter DC EMI Filter L1-Load N BTS L2-Load +12V RPO RTN OUT IN Sync Sync Power Bridge XBus XBus Power Transformer DC- PE Figure A-6 Conext XW+ Block Diagram Accessories Accessory Part Number Conext XW+ Power Distribution Panel 865-1015-01 Conext XW+ Power Distribution Panel (Without AC Breakers) 865-1014-01 Conext XW+ Conduit Box 865-1025-01 Conext XW+ Connection Kit 865
Specifications A–12 975-0240-01-01
B Default Settings Appendix B contains the default configuration settings and ranges for the Conext XW+ Inverter/Charger. Configuration settings can be viewed and changed using the Conext System Control Panel.
Default Settings Default Settings and Ranges Figure B-1 shows how the Conext XW+ configuration menus are organized in the Conext System Control Panel. XW+ 6848 00:Inv [46V] [10s] [70V] [50W] [2s] XW+ 6848 00:Chg [Flooded] Custom Settings [440Ah] [100%] [2-Stage] [Warm] [50V] [180min] [12:00AM] [12:00AM] [Enabled] [64.0V] [57.6V] [57.6V] [54.
Default Settings and Ranges Inverter Menu Item Default Setting Range Step Size Low Batt Cut Out 46 V 40–48 V 0.1 Delay 10s 0–600s 1 High Batt Cut Out 70 V 58–70 V 0.
Default Settings Custom Battery Menu Item Default Settinga Eqlz Support Enabled Enabled, Disabled n/a Eqlz Voltage 64.0 V 54.0–64.0 V 0.1 Bulk Voltage 57.6 V 56.8 V (Gel) 57.2 V (AGM) 40.0–64.0 V 0.1 Absorb Voltage 57.6 V 56.8 V (Gel) 57.2 V (AGM) 40.0–64.0 V 0.1 Float Voltage 54.0 V 55.2 V (Gel) 53.6 V (AGM) 40.0–64.0 V 0.
Default Settings and Ranges Grid-tie Specifications 120 V/240 V 120 V Response Time Anti-islanding reconnect 254.4 V (± 3 V) 127.2 V (± 3 V) 300 s (+1/–0 s) Over frequency disconnect 60.5 Hz (± 0.05 Hz) 60.5 Hz (± 0.05 Hz) 60 ms (± 20 ms) Under frequency disconnect 59.3 Hz (± 0.05 Hz) 59.3 V (± 0.05 Hz) 60 ms (± 20 ms) Over voltage LN fast disconnect 135 V (± 1.5 V) 135 V (± 1.5 V) 60 ms (± 25 ms) Over voltage LN slow disconnect 132 V (± 1.5 V) 132 V (± 1.
Default Settings Gen Support Menu Setting Default Range Step Size GenSupp Mode Disabled Enabled, Disabled n/a GenSupp Amps 48 A 0–48 A 1 Aux Menu Step Size Item Default Range Manual Aux ManualOff ManualOn, ManualOff, Automatic n/a Active Lvl ActiveHigh ActiveHigh, ActiveLow n/a LowBattV LowBattV, HighBattV, LowBattTemp, HighBattTemp, Fault n/a Trigger Level—LowBattVb 46.0 VDC 20.0–58.0 VDC 0.1 Clear Level—LowBattV 48.0 VDC 20.0–58.0 VDC 0.1 Trigger Level—HighBattV 56.
Default Settings and Ranges 975-0240-01-01 Item Default Range AC2 Gen 1 None, Grid1–10, Gen1–10 B–7
Default Settings B–8 975-0240-01-01
Index Numerics D 2-stage charge mode 15 3-stage charge mode 12 default settings, restoring 46 device home screen 13 display screen 8 down arrow button 9 A absorption charging stage 13 AC Coupling 8 AC settings menu default settings 4 description 22 AC Transfer 10 accessories 11 advanced features menu 47 advanced menu 4 APF Mode 15 automatic faults 17 automatic generator start 9 auxiliary output menu default settings 6 description 34 B battery level LEDs 7 battery type 11 bidirectional theory of operati
Index K K1 and K2 relay 11 keypress for system standby mode 10 kW LED 3 system home screen 11 system standby mode 10 system status screen 13 T L LBCO setting 9 load shave 16, 25, 30 M manual faults 17 max battery discharge 21 mechanical specifications 10 menu map 7, 2 meters screen 16 multi-stage charging process 12 multi-unit operation 9 three-stage charge mode 12 time-of-use (TOU) metering 31 troubleshooting fault messages 16 general guidelines 2 motor loads 3 problem loads 3 resistive loads 3 warnin
Schneider Electric www.schneider-electric.com For other country details please contact your local Schneider Electric Sales Representative or visit our website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.