Default Settings and Ranges
975-0240-01-01 B–5
Grid-tie Specifications
Grid Support Menu
120 V/240 V 120 V Response Time
Anti-islanding reconnect 254.4 V (± 3 V) 127.2 V (± 3 V) 300 s (+1/–0 s)
Over frequency disconnect 60.5 Hz (± 0.05 Hz) 60.5 Hz (± 0.05 Hz) 60 ms (± 20 ms)
Under frequency disconnect 59.3 Hz (± 0.05 Hz) 59.3 V (± 0.05 Hz) 60 ms (± 20 ms)
Over voltage LN fast disconnect 135 V (± 1.5 V) 135 V (± 1.5 V) 60 ms (± 25 ms)
Over voltage LN slow disconnect 132 V (± 1.5 V) 132 V (± 1.5 V) 500 ms (± 25 ms)
Over voltage L1/L2 fast disconnect 270 V (± 3 V) 60 ms (± 25 ms)
Over voltage L1/L2 slow disconnect 264 V (± 3 V) 500 ms (± 25 ms)
Under voltage LN fast disconnect 66 V (± 5 V) 66 V (± 5 V) 100 ms (± 25 ms)
Under voltage LN slow disconnect 105.6 V (± 1.5 V) 105.6 V (± 1.5 V) 1000 ms (± 25 ms)
Under voltage L1/L2 slow disconnect 211.2 V (± 3 V) 100 ms (± 25 ms)
Under voltage L1/L2 fast disconnect 132 V (± 10 V) 60 ms (± 25 ms)
Item
Default Range Step Size
Grid Supp Volts
53.0 V
a
a.The setting for Grid Supp Volts must be greater or equal to LBCO+2 V. For
example, if LBCO is 44 V then the minimum Grid Supp Volts is 46 V.
42.0–70.0 V
0.1
Max Sell Amps
b
b.This setting is restricted to the selected external AC1 breaker size.
27 A (XW+ 6848),
20 A (XW+ 5548)
0–27 A (XW+ 6848),
0–20 A (XW+ 5548)
1
Load Shave Amps 48 A 0–48 A 1
Load Shave Start
c
c.When Load Shaving is enabled, if Load Shave Start and Load Shave Stop
are set to the same time, the Conext XW+ load shaves continuously.
12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Load Shave Stop 12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1