Default Settings
B–6 975-0240-01-01
Gen Support Menu
Aux Menu
Connections Menu
Setting Default Range Step Size
GenSupp Mode Disabled Enabled, Disabled n/a
GenSupp Amps 48 A 0–48 A 1
Item
Default Range
Step
Size
Manual Aux ManualOff ManualOn, ManualOff,
Automatic
n/a
Active Lvl ActiveHigh ActiveHigh, ActiveLow n/a
Trigger Src
a
a.The Trigger Src setting (and the settings below Trigger Src) appear only if
Manual Aux setting has been set to Automatic.
LowBattV LowBattV, HighBattV,
LowBattTemp, HighBattTemp,
Fault
n/a
Trigger Level—LowBattV
b
b.Trigger Level, Trigger Delay, Clear Level and Clear Delay do not appear if
Trigger Src is set to Fault.
46.0 VDC 20.0–58.0 VDC
0.1
Clear Level—LowBattV
48.0 VDC 20.0–58.0 VDC
0.1
Trigger Level—HighBattV
56.0 VDC 48.0–64.0 VDC
0.1
Clear Level—HighBattV
52.0 VDC 48.0–64.0 VDC
0.1
Trigger Level—HighBattTemp 45.0°C
30.0–60.0°C
1
Clear Level—HighBattTemp 35.0°C 30.0–60.0°C 1
Trigger Level—LowBattTemp 0.0°C -30.0–10.0°C 1
Clear Level—LowBattTemp 5.0°C -30.0–10.0°C 1
Trigger Delay 1s 0–600s 1
Clear Delay 1s 0–600s 1
Charge Bulk Exit Bulk Exit N/A 0.1
Charge Absorption Exit Absorption Exit N/A 0.1
Heatsink Temperature 100°C -30.0-20.0°C 1
SOC (State of Charge) (with
Conext Battery Monitor only)
25% 0-100% 1
TOD (Time of Day) 12:00 AM 12:00 AM-11:59 PM 1 m
Item Default Range
DCConn HouseBatt1 HouseBatt1–6
ACOut ACLoad1 ACLoad1–10
AC1 Grid 1 None, Grid1–10, Gen1–10