Installation Guide
Table Of Contents
- Conext™ XW+ Inverter/Charger Installation Guide
- Conext™ XW+ Inverter/Charger Installation Guide
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext 120/240VAC Breaker Kit for Conext XW+ PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Conext 3 Phase Breaker Kit for Conext XW+ PDP
- 100A, 125VDC Breaker Master Pack (12 units)
- 80A, 125VDC Breaker Master Pack (12 units)
- 60A, 160VDC Breaker Master Pack (48 units)
- 250A, 160VDC Breaker Master Pack (6 units)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger and Conext XW+ Power Distribution Panel
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW+ units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring a Balanced Three-Phase System
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
- Wiring Diagrams
- Split-Phase to Single-Phase Conversion Instructions
Wiring the Conext XW+ Inverter/Charger and Conext XW+ Power Distribution Panel
3–64 975-0239-01-01 Rev G
This manual is for use by qualified personnel only
3. In the PDP, attach six two-tab power distribution jumpers in the AC breaker
positions as shown in Figure 3-32 on page 3–64.
4. Connect the AC wiring as shown in Figure 3-33.
Figure 3-32 Power Distribution Jumper Installation (Three-Phase)
Pole 1 Pole 2 Pole 3
GRID BYPASS LOADS
GEN
(optional)
Figure 3-33 PDP Three-Phase AC Wiring
GRID BYPASS LOADS
Grid Distribution Panel Generator or PV
Pole 1 Pole 2 Pole 3
INV1 INV3
AC IN 1
L1
AC IN 1
L2
AC IN 1
L3
INV1 INV3
L1 L2 L3
INV2
AC IN 2
INV2
AC IN 2 AC IN 2
Loads distribution panel
INV1 INV3
L1 L2 L3
INV2
AC OUT AC OUT AC OUT
GEN
(optional)