Wiring the Conext XW+ Inverter/Charger and Conext XW+ Power Distribution Panel
3–66 975-0239-01-01 Rev G
This manual is for use by qualified personnel only
2. Connect neutral wiring from INV1, INV2, and INV3 to the neutral bus bar on
the PDP.
3. Connect ground wiring from INV1, INV2, and INV3 to the ground bus bar on
the PDP.
4. Using the labels included with the PDP, re-label the AC breakers as
appropriate.
5. Install the bypass interlock plate, as shown in figure “Bypass Interlock Plate
Installation (Three-Phase)” on page 3–66.
Bypass Interlock Plate Installation (Three-Phase)
To install the custom designed bypass interlock plate:
1. Replace the upper and lower faceplates on the PDP.
2. Place the bypass interlock plate over the breakers, as shown in Figure 3-35,
and secure it in place with the hardware provided.
3. To set it in Normal position, slide the bypass plate to the right, as shown in
Figure 3-35.
Figure 3-35 Installing the custom designed three-phase bypass interlock plate
BYPASS POSITION NORMAL POSITION