Installation Guide
Table Of Contents
- Conext™ XW+ Inverter/Charger Installation Guide
- Conext™ XW+ Inverter/Charger Installation Guide
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext 120/240VAC Breaker Kit for Conext XW+ PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Conext 3 Phase Breaker Kit for Conext XW+ PDP
- 100A, 125VDC Breaker Master Pack (12 units)
- 80A, 125VDC Breaker Master Pack (12 units)
- 60A, 160VDC Breaker Master Pack (48 units)
- 250A, 160VDC Breaker Master Pack (6 units)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger and Conext XW+ Power Distribution Panel
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW+ units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring a Balanced Three-Phase System
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
- Wiring Diagrams
- Split-Phase to Single-Phase Conversion Instructions
Installing the Network
975-0239-01-01 Rev G 4–7
This manual is for use by qualified personnel only
3. Route the cable as shown in Figure 4-6. Route any additional communication
cables through the raceways. Replace the wiring raceways, ensuring not to
pinch the cables. Secure the raceways to the Conduit Box with the screw that
was removed earlier.
Guidelines for Routing the Xanbus Cables
To ensure maximum performance of your network, follow these guidelines when
routing the Xanbus cables.
• Route the cables away from sharp edges that might damage the insulation.
Avoid sharp bends in the cable—no less than a 4-inch (100 mm) radius.
• Allow at least 2 ¼ inches (57 mm) of space behind the wall to accommodate
the depth of the unit and allow room for the cables to bend.
• Allow for some slack in the cable tension.
• Keep the alignment of wire pairs inside the sheath as straight as possible.
• Allow separation between data and power cables (data cables should only
cross over a power cable at right angles).
Figure 4-6 Installing the AC sync and Xanbus cables
Note: In a dual-inverter system, install an AC Sync Cable from INV1 to INV2. In a
triple-inverter system, daisy-chain an AC Sync Cable from INV1 to INV2 and from
INV2 to INV3.
WARNING
XANBUS SHOCK HAZARD
Xanbus cables in contact with DC or AC power can transmit an electric shock.
Do not route the Xanbus cables in the same conduit or panel as the AC and
DC power cabling.
Failure to follow these instructions can result in death or serious injury.