Conext System Control Panel Installation
975-0239-01-01 Rev G 5–3
This manual is for use by qualified personnel only
Installing the SCP via the Xanbus Network
The SCP is connected to the Xanbus network via either of the two Xanbus
network ports located at the bottom of the Conext XW+ chassis (as shown in
Figure 5-1).
For more information about installing a Xanbus-enabled device as part of a
network system, see Chapter 4, “Xanbus Network Installation”.
For wall-mounting and other installation instructions, see the Conext System
Control Panel Owner’s Guide (975-0298-01-01).
WARNING
IGNITION AND FIRE HAZARD
This equipment is not ignition protected. To prevent fire or explosion, do not
install this product in locations that require ignition-protected equipment. This
includes any confined space containing vented batteries, or flammable
chemicals such as, natural gas (NG), liquid petroleum gas (LPG) or gasoline
(Benzine/Petrol).
• Do not install in a confined space with machinery powered by flammable
chemicals, or storage tanks, fittings, or other connections between
components of fuel or flammable chemical systems.
• Do not install the inverter near readily flammable materials such as cloth,
paper, straw, or plastic sheeting. Keep flammable materials a minimum
distance of 600 cm (24 in.) from the top surface and 30 cm (12 in.) from either
side surface and the front of the Conext XW+ Inverter/Charger.
Failure to follow these instructions can result in death or serious injury.
Figure 5-1 Xanbus Port Locations