Electrical Specifications
975-0240-01-01 A–5
Output Power Versus Ambient Temperature
When the internal temperature of the Conext XW+ exceeds a preset limit, it
begins to limit output power automatically to stop maximum internal temperatures
from being exceeded.
Figure A-1 Conext XW+ AC Overload Capability
Note: For the Conext XW+ 6848 model, the power can be limited by the
installed DC and AC breakers. For example, at 8500 W the DC or AC breakers
may disconnect before the 30 minute rating.
10
0
10
1
10
2
10
3
10
4
10
5
10
6
4800
6300
8800
12000
Time in Seconds
L1/L2-Neutral (120 V) Load [W]
Conext XW+ 6848 UL L1-N or L2-N: Imbalanced Line Loading
5 Minutes
30 Minutes
Surge Power Versus Time