This manual is for use by qualified personnel only
Torque Values
Torque values for the Conext XW+
Torque Values for the Conext XW+ Power Distribution Panel
Table 2- 4 Torque Values for AC Wiring (AC Terminals and Ground Bar)
Wire Size Torque Value
AWG mm In-lb N-m
14–10 1.63–2.59 35 4.0
8 3.26 40 4.5
6–4 4.11–5.19 45 5.1
Table 2- 5 Torque Values for the Chassis Ground Lug
Wire Size Torque Value
AWG mm In-lbs N-m
6–4 4.11–5.19 45 5.1
3–2 5.83–6.54 50 5.6
Table 2- 6 Torque Values for the Inverter Battery Terminals
Torque Value
Ft-lbs N-m
15 20.4
Table 2- 7 Torque Values for AC Disconnects and AC Breakers
Wire Size Torque Value
AWG mm In-lb N-m
16–10 1.29–2.59 45 5.1
8 3.26 45 5.1
6–4 4.11–5.19 45 5.1
Table 2- 8 Torque Values for the Ground Bus, AC Neutral Bus, DC Negative Bus,
and DC Positive Bus in the Conext XW+ Power Distribution Panel
Wire Size Torque Value
AWG mm In-lbs N-m
14–10 1.63–2.59 35 4.0
83.26404.5
6–4 4.11–5.19 45 5.1
3–2/0 5.83–9.27 50 5.6