Installation Guide
Table Of Contents
- Conext™ XW+ Inverter/Charger Installation Guide
- Conext™ XW+ Inverter/Charger Installation Guide
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext 120/240VAC Breaker Kit for Conext XW+ PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Conext 3 Phase Breaker Kit for Conext XW+ PDP
- 100A, 125VDC Breaker Master Pack (12 units)
- 80A, 125VDC Breaker Master Pack (12 units)
- 60A, 160VDC Breaker Master Pack (48 units)
- 250A, 160VDC Breaker Master Pack (6 units)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger and Conext XW+ Power Distribution Panel
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW+ units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring a Balanced Three-Phase System
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
- Wiring Diagrams
- Split-Phase to Single-Phase Conversion Instructions
Wiring the Conext XW+ Inverter/Charger and Conext XW+ Power Distribution Panel
3–6 975-0239-01-01 Rev G
This manual is for use by qualified personnel only
The auxiliary output can also be triggered manually using a Conext System
Control Panel or ComBox.
The 12 VDC output can be used to trigger a relay to disconnect batteries from
the inverter/charger when battery voltage or temperature are out of range.
The auxiliary output is also designed to provide the following functions:
• Auxiliary 12 VDC power supply. See AUX+12V Voltage Supply, below.
• Remote Power Off. See AUX-RPO: User Remote Power OFF (RPO), below.
AUX+12V Voltage Supply
DC voltage is available between JU-1 (AUX +12 V) and JU-3 (AUX-COM, signal
return). The power available at these terminals is 12 VDC and maximum current
is 250 mA (3 watts).
AUX+12 V and AUX-COM terminals can be used to power a relay
(3 watts maximum).
AUX +12 V voltage supply can be programmed for different tasks ON and OFF
using the Conext System Control Panel.
Default status of AUX+12 V is OFF.
AUX-RPO: User Remote Power OFF (RPO)
Connecting JU-2 (AUX-RPO) and JU-3 (AUX-COM) terminals together through
an external switch (normal open contact) will provide the system shut off function
if the switch is closed. The external switch, if pressed, overrides the control
provided from the front panel.
Note: The AUX port is connected via an AUX port connector, included with the
Conext XW+ Inverter/Charger.
Figure 3-4 AUX Port Location
AUX port
Note: Additional fuses may be necessary for some installations.