Installation Guide
Table Of Contents
- Conext™ XW+ Inverter/Charger Installation Guide
- Conext™ XW+ Inverter/Charger Installation Guide
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext 120/240VAC Breaker Kit for Conext XW+ PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Conext 3 Phase Breaker Kit for Conext XW+ PDP
- 100A, 125VDC Breaker Master Pack (12 units)
- 80A, 125VDC Breaker Master Pack (12 units)
- 60A, 160VDC Breaker Master Pack (48 units)
- 250A, 160VDC Breaker Master Pack (6 units)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger and Conext XW+ Power Distribution Panel
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW+ units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring a Balanced Three-Phase System
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
- Wiring Diagrams
- Split-Phase to Single-Phase Conversion Instructions
Wiring the Conext XW+ Inverter/Charger with a PDP
975-0239-01-01 Rev G 3–7
This manual is for use by qualified personnel only
To enable the AUX port remote power off function, enable the RPO setting from
the System Control Panel. For more information, see the Conext XW+ Inverter/
Charger Owner’s Guide. If the external switch is cleared (not pressed), the
system can be enabled back from the front panel.
Select an external switch with normal open contact; consult your local system
designer or qualified technician for specific installation instructions.
User Line Wiring
Use twisted pairs of #24 AWG to #12 AWG (0.51mm to 2.05mm) for connections.
Carefully route the wires away from high power load cables to minimize noise
effects on signal integrity.
AUX Port Terminal Assignments
Wiring the Conext XW+ Inverter/Charger with a PDP
Table 3-1 User Connector Terminals and Functions
Pin Reference Name Function
JU-1 AUX+12V +12 V User
Voltage Supply
+12 VDC Voltage source: 250 mA
maximum
JU-2 AUX-RPO Remote Power
Off
Remote Power Off Logic Level:
Active Low. Activating this signal
shuts down system operation.
JU-3 AUX-COM Common
Ground
Reference
Return Common Ground
Reference for 12 V, Remote Power
Off signals.
JU-4 EXT_TS_OUT External
Transfer switch:
Output signal
Open collector type drive circuit
(30V/0.5A max)
JU-5 EXT_TS_IN External
Transfer switch:
Input signal
External Transfer switch: Low
signal range:(0-5V) High signal
range:10-28V with the
consumption of 8mA@12V and
10mA@24V.
NOTICE
OVERLOADING THE DISTRIBUTION PANEL
The amount of power that can be fed into a distribution panel and the means
and location for feed-in, must be in accordance with NEC 2008 article 690.64
or the current requirements of the local electrical code.
Failure to follow these instructions can result in damage to equipment.