Installation Guide
Table Of Contents
- Conext™ XW+ Inverter/Charger Installation Guide
- Conext™ XW+ Inverter/Charger Installation Guide
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext 120/240VAC Breaker Kit for Conext XW+ PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Conext 3 Phase Breaker Kit for Conext XW+ PDP
- 100A, 125VDC Breaker Master Pack (12 units)
- 80A, 125VDC Breaker Master Pack (12 units)
- 60A, 160VDC Breaker Master Pack (48 units)
- 250A, 160VDC Breaker Master Pack (6 units)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger and Conext XW+ Power Distribution Panel
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW+ units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring a Balanced Three-Phase System
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
- Wiring Diagrams
- Split-Phase to Single-Phase Conversion Instructions
Wiring the Conext XW+ Inverter/Charger with a PDP
975-0239-01-01 Rev G 3–15
This manual is for use by qualified personnel only
To connect the Conext XW+ Power Distribution Panel (PDP) to the Battery
Bank:
1. Connect your battery cables (not included) to the PDP. Connect the negative
battery cable to the DC Negative Bus, and the positive battery cable to the
input end of the GJ250A 160 VDC, 3/8" stud DC breaker (pre-installed in the
PDP), as shown in Figure 3-9 on page 3–16.
2. Route your battery cables from the PDP, through your preferred conduit path,
to the battery location. Do not connect the cables to the battery yet.
Note: To properly attach and torque the positive cable to the DC breaker, you
may need to temporarily remove the breaker from the rail.
Note: Before connecting the DC cables from the PDP to the battery, perform the
procedures in “Making AC Connections” on page 3–17.