Wiring the Conext XW+ Inverter/Charger and Conext XW+ Power Distribution Panel
3–28 975-0239-01-01 Rev G
This manual is for use by qualified personnel only
To connect the Conext XW+ Power Distribution Panel to the Inverter Load Sub-Panel and Utility Grid:
1. Connect L1 (from the L1 output jumper) and L2 (from the L2 output jumper),
Neutral, and Ground to your inverter load sub-panel.
2. Connect the ground wire between the PDP and the main AC Panel (utility
grid).
3. Connect Neutral from the PDP to the main AC panel (utility grid).
4. Connect L1 and L2 from the input side of the 60 A, 120/240 VAC, two-pole,
Type QOU AC1 breaker (L1 and L2 jumpers) to the main AC panel (utility
grid).
Figure 3-15 Wiring the PDP to the Inverter Load Sub-Panel or Utility Grid
AC INAC OU T AC IN
GRID
(AC1)
AC
LOAD
GEN
(AC2)
NL1L2NL1L2NL1 L2
L2L1
1
2
1. Main utility panel
2. Inverter load sub-panel
Actual wiring requirements may vary.
Cable routing may vary. See Knockout Selection
on page 2-5 and Communications Network
Preparation on page 2-12.
For torque values, see page 2-16 and 2-17.
LEGEND
Grounding
wire
Neutral
Hot L1
Hot L2