Basic Functional Test Single Inverter
975-0239-01-01 Rev G 3–29
This manual is for use by qualified personnel only
Basic Functional Test – Single Inverter
Complete the following steps to perform a basic functional test of the Conext
XW+ Inverter/Charger. If any test fails, refer to the Troubleshooting section in the
Conext XW+ Inverter/Charger Owner’s Guide for assistance.
Confirming All Connections
After the AC and DC wiring have been installed and connected, check that all
connections are correct and secure, and re-secure the AC access panel.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
This equipment must only be installed and serviced by qualified electrical
personnel.
Never operate energized with covers removed
Energized from multiple sources. Before removing covers identify all
sources, de-energize, lock-out, and tag-out and wait 2 minutes for circuits to
discharge
Always use a properly rated voltage sensing device to confirm all circuits are
de-energized.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Remove watches, rings, or other metal objects.
This equipment must only be installed and serviced by qualified electrical
personnel.
Keep sparks and flames away from the batteries.
Use tools with insulated handles.
Wear protective glasses, gloves and boots.
Do not lay tools or other metal parts on top of batteries.
Failure to follow these instructions will result in death or serious injury.