Installation Guide
Table Of Contents
- Conext™ XW+ Inverter/Charger Installation Guide
- Conext™ XW+ Inverter/Charger Installation Guide
- About This Guide
- Important Safety Instructions
- Contents
- Introduction
- Overview
- Optional Accessories
- Conext XW+ Conduit Box
- Conext XW+ Power Distribution Panel
- Conext XW+ Connection Kit for INV2 INV3 PDP
- Conext 120/240VAC Breaker Kit for Conext XW+ PDP
- Conext MPPT 60 150 Solar Charge Controller
- Conext MPPT 80 600 Solar Charge Controller
- Conext System Control Panel
- Conext Automatic Generator Start
- Conext ComBox
- Conext Battery Monitor
- Conext 3 Phase Breaker Kit for Conext XW+ PDP
- 100A, 125VDC Breaker Master Pack (12 units)
- 80A, 125VDC Breaker Master Pack (12 units)
- 60A, 160VDC Breaker Master Pack (48 units)
- 250A, 160VDC Breaker Master Pack (6 units)
- Pre-Installation and Wall-Mounting
- Wiring the Conext XW+ Inverter/ Charger and Conext XW+ Power Distribution Panel
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW+ Inverter/Charger with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW+ units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring a Balanced Three-Phase System
- Wiring the Conext XW+ Inverter/Charger without a PDP
- Xanbus Network Installation
- Conext XW+ Inverter/Charger Accessories Installation
- Specifications
- Wiring Diagrams
- Split-Phase to Single-Phase Conversion Instructions
Wiring the Conext XW+ Inverter/Charger and Conext XW+ Power Distribution Panel
3–36 975-0239-01-01 Rev G
This manual is for use by qualified personnel only
Figure 3-22 Functional Test for Single Inverter Systems
AC OUT
LL2NL1
AC
IN
AC
O
UT
AC OUT
AC
IN
G
RI
D
(
A
C
1
)
AC
L
O
A
D
G
E
N
(
A
C
2)
N
L1
L2
N
L1
L2
L2
N
N
L1
L1
L
2
Check/verify all
wiring and cable
connections
Measure DC Voltage and
confirm the correct
polarity at all of the cable
connections
Within tolerance?
44 to 64 volts for a 48~volt system
Is polarity on cables correct?
Check Battery Bank.
Recharge by external
charger if necessary.
Correct Polarity on Cable
Connections.
Apply DC Power
Check display for
startup self-test
If unit powers up in
enable operating mode
Enable Inverter
Check for Faults
Faults?
Correct fault condition.
Restart Functional Test.
Consult Troubleshooting
section in the Conext
XW+ Owner’s Guide.
Restart functional test.
Close AC Load
breaker.
Confirm operation
of AC Load.
Open AC Load
breaker.
Proceed to
Charger Functional
Test
Within range?
Check AC Voltage
Press the Startup/
Shutdown and Equalize
buttons simultaneously
to enable invert mode.
is displayed briefly.
Yes
Yes
No
No
No
Press the Startup/
Shutdown button
momentarily.