Datasheet
2
Operating rate <= 18000 cycles/hour no-load
<= 1200 cycles/hour under load
Mechanical durability 10000000 cycles
Electrical durability 100000 cycles for resistive load
Average consumption 1.2 VA 60 Hz
Average coil consumption in VA 1.2 at 60 Hz
Drop-out voltage threshold >= 0.15 Uc
Operating time 20 ms
Reset time 20 ms
Average resistance 180 Ohm at 20 °C +/- 15 %
Rated operational voltage limits 19.2...26.4 V AC
Safety reliability data B10d = 100000
Protection category RT I
Operating position Any position
Product weight 0.037 kg
Device presentation Complete product
Compatibility code RXM
Environment
Dielectric strength 1300 V AC between contacts with micro disconnection insulation
2000 V AC between coil and contact with reinforced insulation
2000 V AC between poles with basic insulation
Product certifications RoHS
CE
GOST
Lloyd's
CSA
REACH
UL
Standards EN/IEC 61810-1
UL 508
CSA C22.2 No 14
Ambient air temperature for storage -40...85 °C
Ambient air temperature for operation -40...55 °C
Vibration resistance 3 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 5 cycles in operation)
5 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 5 cycles not operating)
IP degree of protection IP40 conforming to EN/IEC 60529
Shock resistance 10 gn in operation
30 gn not operating
Pollution degree 2
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0801 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months