0098441113480, V2.00, 03.2011
SD315O 4 Installation
Drive for stepper motors 35
Figure 4.2 Mounting distances and air circulation
The specified continuous current is applicable if the following distances
are maintained and the device is installed vertically.
• At least 10 mm of free space is required in front of the device.
• At least 50 mm of free space is required above the device.
• At least 30 mm of free space is required for "d".
• At least 200 mm of free space is required below the device to allow
for cable installation without bends.
If other parts are mounted in the areas mentioned, the possible contin-
uous current is reduced.
Mounting the device The product can be mounted directly via the narrow or wide mounting
surface with two M4 screws. The product can optionally be snapped
onto a standard TH35 rail (accessories) as per IEC 60715 (DIN rail 35
mm). See chapter 3.2.1 "Dimensions", for the dimensions of the mount-
ing holes.
왘 Mount the device in a vertical position (±10°).
왘 Use connection elements (busbars, shield clamps or similar) to
route the cable and connect the shield.
NOTE: Painted surfaces have an insulating effect. Before mounting the
device to a painted mounting plate, remove all paint across a large area
of the mounting points until the metal is completely bare.
dd