SD315O 11 Extract
Drive for stepper motors 81
11.2 Extract for commissioning
11.2.1 Setting the nominal current
NOTE: Setting a nominal current higher than the nominal current of the
motor may damage or destroy the motor.
Parameter switch S1 allows you to set the nominal current.
왘 Set the nominal current of the motor by means of parameter switch
S1.
NOTE: If the nominal current of the motor is >7.5 A, you must set a
value of ≤67 % for the current reduction.
Switch setting S1 Nominal current of motor
0 (factory setting) [A] 3
1[A]3.7
2[A]4.4
3[A]4.8
4[A]5.2
5[A]5.5
6[A]5.8
7[A]6.2
8[A]6.6
9[A]7
A[A]7.5
B[A]8
C[A]8.5
D[A]9
E[A]9.5
F[A]10