Input 120-277Vac +/-10% 50/60 Hz
Output 120Vac 277Vac
1000 W max. tungsten
incandescent load
¼ hp max. motor load 277Vac
1000 VA max. ballast load 1800 VA max. ballast load
Operating Temperature 32 - 122° F (0 - 50°C)
Humidity 0 - 90% RH Non-condensing
Time Delay Adjustment
Normal 0.5 - 30 minutes
Walk Through Mode 2 minutes if no activity is detected after 30 seconds
Test Mode 15 seconds
Light Level adjustment 0.5 - 250 FC
Detection 180° passive infrared (PIR)
Audible Alert Selectable
Service Switch OFF / Auto / ON
Manual Operation Push-button ON/OFF
Lens Impact Resistant
Relay Switching 0° +/- 500uS
Standards UL and cUL Listed FCC Part 15,
Home and Ofce Use (Class B) Title 24 Certied
*For Diagram see technical section page 19
Catalog Number Description
SLSUWS1277UW White
SLSUWS1277UI Ivory
SLSUWS1277UG Gray
SLSUWS1277UL Light Almond
SLSUWS1277UB Black
OCCUPANCY SENSORS
+
WALL SWITCH OCCUPANCY SENSORS
Product Features
Available in white, ivory, gray, light
almond and black with matching
wall switch cover plate
• Color matching multi-segmented
lens
• Selectable auto-on and manual-
on modes
• 120-277Vac 50/60Hz input
• 180° eld of view
1000 sq. ft. major motion and
300 sq. ft. minor motion coverage
area
• Light level sensor
• Walk-through mode
• Adjustable light level, time delay
and sensitivity
• Red LED motion indicator
• For use with electronic and
magnetic ballasts
• No neutral connection, minimum
load or power pack required
• UL and cUL Listed for United
States and Canada
• Test mode (15 second time delay)
• Five-year warranty
Schneider Electric Single Circuit PIR Wall Switch Occupancy Sensor with Light Level features
passive infrared (PIR) technology to conveniently control lighting in ofces, private bathrooms,
utility rooms and employee break rooms. Low prole sensor available in white, ivory, gray, light
almond and black with color-matched segmented lens to meet any décor need.
Adaptive Technology: New patent pending technology employs advanced algorithms to achieve
convenient energy savings and reduced lamp and ballast maintenance
Walk-Through Mode: To maximize energy savings and reduce waste, the sensor detects when
areas are briey occupied as a result of an occupant walking through and turns off lighting
based on a shorter time delay.
Light Level Sensor Mode: Each sensor includes an adjustable light level sensor to hold off
articial lighting when adequate natural light is present. When natural light levels drop below the
threshold, the sensor will turn on articial lighting in occupied spaces.
The sensor does not require a neutral connection or minimum load, making it great for retrots.
Easily replaces an existing wall switch using existing wiring – no wiring modications required.
Matching wall switch cover plate makes retrots clean and simple.
Commercial Grade Occupancy Sensor
Ultrasonic Single Circuit Wall Switch
Single Circuit Wall Switch
Occupancy Sensor